Low-voltage cable footage calculator
For each device type, cable footage = devices × cables per device × (average run + service loop), plus waste. Divide the total by 1,000 ft and round up for the boxes to buy.
Enter your own counts and runs below for the totals, and download them as a CSV. A row past 295 ft gets a warning. It runs in your browser; nothing you type is saved or sent. Copy link shares your rows.
How do you calculate low-voltage cable footage?
Work out each device type's footage, add the rows, and turn the total into boxes:
ft per row = count × cables per device × (average run + service loop) × (1 + waste %) boxes = ⌈ft ÷ 1,000⌉
This is the calculator's example, not a benchmark. Its counts, runs and loops are made up. On the data drop row, 48 devices with 2 cables each are 96 cables. At 150 ft plus a 20 ft loop, with 10% waste, that's 17,952 ft, or 18 boxes. The 5 rows come to 26,026 ft, 27 boxes.
Why does the calculator warn at 295 ft?
A Cat 5e, Cat 6 or Cat 6A horizontal link, from the patch panel to the outlet, can be up to 90 m (295 ft) under ANSI/TIA-568. The service loop is cable in the link, so the check is on the run plus the loop, not the run alone. A row whose average passes 295 ft is flagged; its footage still counts.
An average under 295 ft can still hide single runs over it. Check the longest runs on their own; the post on the 295 ft Cat6 limit covers the fixes, from a closer telecom room to fiber.
Where should the average run come from?
From measured runs on the drawings. A run's length is set by the distance from the device to its telecom room or head end, so it changes across the building. Measure a few near the room, in the middle and at the far end, and use their average per device type.
In a low-voltage takeoff in TakeOn, each run is drawn on the plan. With the Low voltage starter pack's cable run template, the service loop and slack are added for you and any run past 295 ft is flagged. The guide to a low-voltage takeoff covers what else goes into the bid.
Related tools
- Fire alarm battery calculator: Size a fire alarm panel's standby battery in amp-hours from your devices' standby and alarm currents, the NFPA 72 standby and alarm times and a safety margin.
- Sleeve fill calculator: How many cables fit in a sleeve through a wall: the fill % against your firestop listing's max fill, the NEC 60% nipple and Table 1 figures for reference, and how many more cables fit.
- Wire ampacity calculator: Get a conductor's allowable ampacity from NEC Table 310.16, derated for ambient and conductor count and capped at the 75 °C or 60 °C termination rating.
- Wire size calculator: Find the smallest wire for a load from NEC Table 310.16, with the 125% continuous-load factor, 240.4(D) breaker limits and an optional voltage-drop limit.
- Voltage drop calculator: Get a run's voltage drop in volts and percent from the NEC Chapter 9 Table 8 resistance, single- or three-phase, or the longest run that stays within a target drop.
- Metric voltage drop calculator: Voltage drop in metres: type the cable's mV/A/m from its datasheet, the current, the length and the voltage for the drop in volts and percent, and a pass or fail against your own limit.
- Ground wire size calculator: Size the equipment grounding conductor from NEC Table 250.122, and upsize it in proportion when the phase conductors were upsized for voltage drop (250.122(B)).
- Neutral conductor size calculator: Size a feeder or service neutral from the NEC 220.61 unbalanced load, with the 70% reduction over 200 A, and the Table 250.122 or 250.102(C)(1) minimum.
- Motor circuit calculator: wire, breaker and ground size: Size a single motor's branch circuit from NEC Article 430: full-load current, the conductor at 125%, the largest breaker or fuse, the ground wire and the overload.
- Transformer amps calculator: Get a transformer's primary and secondary full-load amps from its kVA, phase and voltages, with a table for the standard kVA ratings.
- Ohm's law calculator: Enter any two of voltage, current, resistance and power to get the other two, with the formula used, for DC and resistive circuits.
- Conduit support spacing calculator: Get the NEC maximum distance between conduit supports and from a box for EMT, IMC, RMC, PVC, RTRC, ENT, FMC, LFMC and LFNC, and the minimum strap count for a run.
- Conduit fill and size calculator: What size conduit do you need? Mix wire types and sizes, grounds included, and get the smallest conduit that fits plus the fill % in every trade size, from NEC Chapter 9.
- Metric conduit fill calculator: Conduit fill in millimetres: type the conduit's internal diameter and each cable's overall diameter for the fill %, a pass or fail against your own limit and the largest cable that still fits.
- All free tools for electrical estimators
- The 295 ft limit, and what to do about it: how long a Cat6 run can be
- What goes into one: what is a low-voltage takeoff
-
How do you estimate low-voltage cable footage?
For each device type, multiply the device count by the cables pulled to each device, then by the average run plus the service loop. Add your waste %. Add the rows for the total and divide by 1,000 ft, rounded up, for the boxes to buy.
-
What is a service loop and how much should I allow?
A service loop is extra cable left coiled at one or both ends of a run, so the cable can be re-terminated or the device moved later. Allow what the project specification or your own standard calls for, both ends combined, per run. The calculator's loops are only examples.
-
Why does a row warn at 295 ft?
Because 295 ft (90 m) is the permanent-link limit for Cat 5e, Cat 6 and Cat 6A horizontal cabling under ANSI/TIA-568. A row whose average run plus loop passes it is flagged. It's a warning, not a cap, since the row may be another kind of cable.
-
How many 1,000 ft boxes of cable do I need?
The total footage divided by 1,000, rounded up, if every row is the same cable. If the rows are different cables, round up each row on its own. The calculator shows both, and the CSV has each row's boxes.
-
What waste % should I use for cable?
Your own, from what you bought against what you measured on past jobs. A waste or make-up percentage covers box ends, cut-offs and terminations on footage you already have. The example's figure is only an example.
-
Does this calculator save or send what I type?
No. The calculator runs entirely in your browser. Nothing you enter is saved or sent anywhere, and no account is needed. Copy link puts your rows in the link itself, so only the people you send it to see them.
Measured, not averaged
Draw every cable run on the plans.
In TakeOn, draw each run on the PDF plans. The Low voltage starter pack's cable run template adds its service loop and slack, and flags any run past 295 ft. No credit card needed.