Metric conduit fill calculator

Conduit fill is the cables' total cross-section area divided by the conduit's internal area: Σ (count × π d² ÷ 4) ÷ (π D² ÷ 4), with every diameter in millimetres. If that is at or under your fill limit, the cables fit.

Type the conduit's internal diameter and each cable's overall diameter from the makers' data. You get the fill %, a pass or fail against your limit and the largest cable you could still add, with the working shown. It runs in your browser; nothing you type is saved or sent.

Working to the NEC in inches and trade sizes? Use the conduit fill and size calculator.

Example values, not benchmarks. Replace them with your own.

Conduit

The bore, from the conduit maker's data: not the size on the label.

40% is NEC's limit for three or more cables; set your own wiring rules' figure.

Cables — one row per size
Area 132.5 mm²
Area 23.8 mm²

Enter each cable's overall diameter from its datasheet. The example diameters are made up. There are no built-in tube or cable tables.

Fill
27.3% · Within 40%
Largest added cable
9.62 mm
Cables
4

The largest added cable is the biggest overall diameter one more cable can have and keep the fill within your limit, rounded down to 0.01 mm.

The formula, with your numbers

conduit area = π × 27² ÷ 4 = 572.6 mm²
cable area   = 3 × π × 7.5² ÷ 4 + 1 × π × 5.5² ÷ 4 = 156.3 mm²
fill         = 156.3 mm² ÷ 572.6 mm² = 27.3%: within the 40% limit
largest added cable = √(40% × 27² − 3 × 7.5² − 1 × 5.5²)
                    = √(291.6 − 199) = 9.62 mm

Code-neutral, and not code advice. Every figure is yours: the conduit's bore, the cables' diameters and the limit. The calculator has no built-in tube or cable tables and doesn't use the BS 7671 or AS/NZS space-factor methods. Check the result against the wiring rules that apply to the job.

How do you work out conduit fill in millimetres?

Add up the cables' areas, divide by the conduit's area, and compare with the limit:

conduit area = π × D² ÷ 4
cable area   = Σ count × π × d² ÷ 4
fill %       = cable area ÷ conduit area
largest added cable = √(limit × D² − Σ count × d²)

This is the calculator's example, not any maker's product. Its diameters are made up. A 27 mm bore has an area of 572.6 mm². 3 × 7.5 mm and 1 × 5.5 mm cables take 156.3 mm², so the fill is 27.3%, within a 40% limit. The room left is 40% × 27² − 199 = 92.6 mm², so one more cable up to 9.62 mm overall would still fit.

Why is there no conduit or cable table?

Conduit bores and cable diameters vary by maker and by product, and the fill limit depends on the wiring rules the job is built to. So the calculator asks for all three and doesn't guess any of them. The 40% it starts with is NEC's limit for three or more cables; change it to your own wiring rules' figure.

It is a plain area check. It doesn't reproduce the BS 7671 or AS/NZS space-factor methods, their tables or any other wiring rules' sizing method, and it isn't advice on them.

Related tools

  • Conduit support spacing calculator: Get the NEC maximum distance between conduit supports and from a box for EMT, IMC, RMC, PVC, RTRC, ENT, FMC, LFMC and LFNC, and the minimum strap count for a run.
  • Conduit fill and size calculator: What size conduit do you need? Mix wire types and sizes, grounds included, and get the smallest conduit that fits plus the fill % in every trade size, from NEC Chapter 9.
  • Wire ampacity calculator: Get a conductor's allowable ampacity from NEC Table 310.16, derated for ambient and conductor count and capped at the 75 °C or 60 °C termination rating.
  • Wire size calculator: Find the smallest wire for a load from NEC Table 310.16, with the 125% continuous-load factor, 240.4(D) breaker limits and an optional voltage-drop limit.
  • Voltage drop calculator: Get a run's voltage drop in volts and percent from the NEC Chapter 9 Table 8 resistance, single- or three-phase, or the longest run that stays within a target drop.
  • Metric voltage drop calculator: Voltage drop in metres: type the cable's mV/A/m from its datasheet, the current, the length and the voltage for the drop in volts and percent, and a pass or fail against your own limit.
  • Ground wire size calculator: Size the equipment grounding conductor from NEC Table 250.122, and upsize it in proportion when the phase conductors were upsized for voltage drop (250.122(B)).
  • Neutral conductor size calculator: Size a feeder or service neutral from the NEC 220.61 unbalanced load, with the 70% reduction over 200 A, and the Table 250.122 or 250.102(C)(1) minimum.
  • Motor circuit calculator: wire, breaker and ground size: Size a single motor's branch circuit from NEC Article 430: full-load current, the conductor at 125%, the largest breaker or fuse, the ground wire and the overload.
  • Transformer amps calculator: Get a transformer's primary and secondary full-load amps from its kVA, phase and voltages, with a table for the standard kVA ratings.
  • Ohm's law calculator: Enter any two of voltage, current, resistance and power to get the other two, with the formula used, for DC and resistive circuits.
  • Fire alarm battery calculator: Size a fire alarm panel's standby battery in amp-hours from your devices' standby and alarm currents, the NFPA 72 standby and alarm times and a safety margin.
  • Low-voltage cable footage calculator: Turn device counts into cable footage and 1,000 ft boxes: cables per device, average run and service loop per device type, plus waste, with a 295 ft check.
  • Sleeve fill calculator: How many cables fit in a sleeve through a wall: the fill % against your firestop listing's max fill, the NEC 60% nipple and Table 1 figures for reference, and how many more cables fit.
  • Metric electrical takeoff: TakeOn in metres and m², with 1:100 scales and price per metre
  • All free tools for electrical estimators

Questions

Frequently asked

Can't find an answer? Email contact@takeonbid.com — we read every one.

  • How do you calculate conduit fill in mm?

    Work out each cable's cross-section area from its overall diameter (π × d² ÷ 4), multiply by how many there are, and add the rows. Divide that by the conduit's internal area (π × D² ÷ 4, from its internal diameter). The answer is the fill %. Because π ÷ 4 is on both sides, it is the same as the sum of count × d² divided by D².

  • What fill limit should I use?

    Your own wiring rules', the project specification's or the conduit maker's. The calculator starts at 40%, NEC's limit for three or more cables; change it to your own wiring rules' figure. It doesn't choose a limit for you and doesn't change it with the number of cables.

  • Which diameters do I enter?

    The conduit's internal diameter (its bore) from the maker's data, not the size printed on it, and each cable's overall diameter from its datasheet. The calculator has no built-in conduit or cable tables, so every figure is yours, and the example diameters are made up.

  • What does "largest added cable" mean?

    The biggest overall diameter one more cable can have and keep the fill within your limit: √(limit × D² − Σ count × d²), rounded down to 0.01 mm. Compare it with the next cable's datasheet diameter. "None fits" means the conduit is at the limit, over it, or too close under it for even a 0.01 mm cable.

  • Does this follow BS 7671 or AS/NZS 3000?

    No. It is a plain area-ratio check with the figures you type. It doesn't use the BS 7671 or AS/NZS space-factor methods or their tables, and it isn't advice on any wiring rules. Check your conduit and cable sizing against the rules that apply to the job.

  • Is there an NEC version with trade sizes?

    Yes: the conduit fill and size calculator uses NEC Chapter 9's conduit and conductor tables in inches and trade sizes, and the 53% / 31% / 40% limits by conductor count.

  • Does this calculator save or send what I type?

    No. The calculator runs entirely in your browser. Nothing you enter is saved or sent anywhere, and no account is needed. Copy link puts your figures in the link itself, so only the people you send it to see them.

From takeoff to bid

Measure the conduit, then price it.

TakeOn measures conduit runs off your PDF drawings, in metres in a metric workspace, and turns them into a priced bid. No credit card needed.