Metric voltage drop calculator

Voltage drop (V) = mV/A/m × current (A) × length (m) ÷ 1000, with the cable's mV/A/m figure, the design current and the one-way length in metres. Divide by the nominal voltage for the percent: 10 mV/A/m × 20 A × 30 m is 6.00 V, or 2.61% of 230 V.

Type the mV/A/m from the cable's datasheet or your wiring rules, pick 230 V, 400 V or your own voltage, and add your limit if you want a pass or fail. The working is shown. It runs in your browser; nothing you type is saved or sent.

Working to the NEC in feet? Use the voltage drop calculator.

Example values, not benchmarks. Replace them with your own.

Cable and circuit

From the cable maker's datasheet or your wiring rules' table: the single-phase figure for a 230 V circuit, the three-phase one for 400 V. The example is made up.

Source to load, measured once: the mV/A/m figure already counts the return path.

Your wiring rules' or the specification's figure. There is no default.

Voltage drop
2.61% 6.00 V
Voltage at the load
224.00 V
Against your limit
No limit set

The formula, with your numbers

drop (V)     = 10 mV/A/m × 20 A × 30 m ÷ 1000 = 6.00 V
drop (%)     = 6.00 V ÷ 230 V = 2.61%
at the load  = 230 V − 6.00 V = 224.00 V

Code-neutral, and not code advice. Every figure is yours: the mV/A/m, the current, the length, the voltage and the limit. The calculator has no built-in cable tables and no default limit, and it isn't BS 7671 or AS/NZS advice. Check the result against the wiring rules that apply to the job.

How do you work out voltage drop in metres?

Multiply the cable's figure by the current and the length, then compare with the voltage:

drop (V) = mV/A/m × A × m ÷ 1000
drop (%) = drop (V) ÷ nominal voltage × 100

This is the calculator's example, not any cable's figure. Its 10 mV/A/m is made up. Carrying 20 A over 30 m, the drop is 10 × 20 × 30 ÷ 1000 = 6.00 V. On a 230 V circuit that is 2.61%, leaving 224.00 V at the load. Whether that is acceptable depends on the limit your wiring rules or specification set.

The length is one way. A mV/A/m figure covers the whole circuit, return conductor included, and is given separately for single- and three-phase circuits, so there is no 2 or √3 in the formula.

Why is there no cable table or default limit?

A cable's mV/A/m depends on its maker, its size, its conductor, how it is installed and the circuit type, and the acceptable drop depends on the wiring rules the job is built to. So the calculator asks for both and doesn't guess either.

It doesn't reproduce the BS 7671 or AS/NZS tables or work the drop from a conductor's resistance, which needs temperature and reactance assumptions. It isn't advice on any wiring rules.

Related tools

  • Wire ampacity calculator: Get a conductor's allowable ampacity from NEC Table 310.16, derated for ambient and conductor count and capped at the 75 °C or 60 °C termination rating.
  • Wire size calculator: Find the smallest wire for a load from NEC Table 310.16, with the 125% continuous-load factor, 240.4(D) breaker limits and an optional voltage-drop limit.
  • Voltage drop calculator: Get a run's voltage drop in volts and percent from the NEC Chapter 9 Table 8 resistance, single- or three-phase, or the longest run that stays within a target drop.
  • Ground wire size calculator: Size the equipment grounding conductor from NEC Table 250.122, and upsize it in proportion when the phase conductors were upsized for voltage drop (250.122(B)).
  • Neutral conductor size calculator: Size a feeder or service neutral from the NEC 220.61 unbalanced load, with the 70% reduction over 200 A, and the Table 250.122 or 250.102(C)(1) minimum.
  • Motor circuit calculator: wire, breaker and ground size: Size a single motor's branch circuit from NEC Article 430: full-load current, the conductor at 125%, the largest breaker or fuse, the ground wire and the overload.
  • Transformer amps calculator: Get a transformer's primary and secondary full-load amps from its kVA, phase and voltages, with a table for the standard kVA ratings.
  • Ohm's law calculator: Enter any two of voltage, current, resistance and power to get the other two, with the formula used, for DC and resistive circuits.
  • Conduit support spacing calculator: Get the NEC maximum distance between conduit supports and from a box for EMT, IMC, RMC, PVC, RTRC, ENT, FMC, LFMC and LFNC, and the minimum strap count for a run.
  • Conduit fill and size calculator: What size conduit do you need? Mix wire types and sizes, grounds included, and get the smallest conduit that fits plus the fill % in every trade size, from NEC Chapter 9.
  • Metric conduit fill calculator: Conduit fill in millimetres: type the conduit's internal diameter and each cable's overall diameter for the fill %, a pass or fail against your own limit and the largest cable that still fits.
  • Fire alarm battery calculator: Size a fire alarm panel's standby battery in amp-hours from your devices' standby and alarm currents, the NFPA 72 standby and alarm times and a safety margin.
  • Low-voltage cable footage calculator: Turn device counts into cable footage and 1,000 ft boxes: cables per device, average run and service loop per device type, plus waste, with a 295 ft check.
  • Sleeve fill calculator: How many cables fit in a sleeve through a wall: the fill % against your firestop listing's max fill, the NEC 60% nipple and Table 1 figures for reference, and how many more cables fit.
  • Metric electrical takeoff: TakeOn in metres and m², with 1:100 scales and price per metre
  • All free tools for electrical estimators

Questions

Frequently asked

Can't find an answer? Email contact@takeonbid.com — we read every one.

  • How do you calculate voltage drop with mV/A/m?

    Multiply the cable's mV/A/m figure by the current in amps and the one-way length in metres, then divide by 1000 to get volts. Divide that by the nominal voltage for the percent. For a 10 mV/A/m cable carrying 20 A over 30 m on 230 V, that is 6.00 V, or 2.61%.

  • Where does the mV/A/m figure come from?

    From the cable maker's datasheet, or from the voltage drop table in the wiring rules you work to. It depends on the cable's size, its conductor material, how it is installed and whether the circuit is single- or three-phase. The calculator has no built-in table, so you type the figure, and the example value on the page is made up.

  • Do I use the single-phase or the three-phase mV/A/m?

    The one for your circuit: the single-phase figure for a 230 V single-phase circuit and the three-phase figure for a 400 V three-phase one. Published figures are already given per circuit type, so the calculator doesn't multiply by 2 or √3; the voltage only sets what the percent is taken of.

  • Should I enter the one-way length or the round trip?

    The one-way length, from the source to the load. A mV/A/m figure already counts the return conductor, so entering the round trip would double the answer.

  • What voltage drop limit should I use?

    The one in the wiring rules that apply to the job, or the project specification's. The calculator has no default: leave the limit blank to see the drop alone, or type your figure for a pass or fail with the working.

  • Does this follow BS 7671 or AS/NZS 3000?

    No. It multiplies the figures you type and doesn't contain or apply any wiring rules' tables, limits or methods. It isn't advice on BS 7671, AS/NZS 3000 or AS/NZS 3008. Check your cable sizing against the rules that apply to the job.

  • Is there an NEC version in feet?

    Yes: the voltage drop calculator works from the NEC Chapter 9 Table 8 conductor resistance, with lengths in feet and US wire sizes, and can find the longest run for a target drop.

  • Does this calculator save or send what I type?

    No. The calculator runs entirely in your browser. Nothing you enter is saved or sent anywhere, and no account is needed. Copy link puts your figures in the link itself, so only the people you send it to see them.

From takeoff to bid

Measure the runs, then price them.

TakeOn measures cable runs off your PDF drawings, in metres in a metric workspace, and turns them into a priced bid. No credit card needed.