Voltage drop calculator
Voltage drop = 2 × length × resistance × current ÷ 1000 for a single-phase circuit (√3 instead of 2 for three-phase), with the one-way length in feet and the resistance per 1000 ft from NEC Chapter 9 Table 8. 100 ft of 12 AWG copper carrying 16 A on 120 V drops 6.34 V, or 5.28%, past both the 3% and the 5% the NEC's informational notes suggest.
Enter the circuit and the run for the drop in volts and percent, or switch to Max distance for the longest run that stays within a target. Based on NFPA 70, 2023 edition. It runs in your browser; nothing you type is saved or sent.
Working in meters with a cable's mV/A/m, or not to the NEC? Use the metric voltage drop calculator, with your own figures and limit.
How do you calculate voltage drop?
The calculator uses the conductor's DC resistance at 75 °C from Chapter 9 Table 8, the K-factor method estimators already know:
single-phase VD = 2 × L × R × I ÷ 1000 three-phase VD = √3 × L × R × I ÷ 1000 drop % = VD ÷ system voltage × 100 max distance L = VD allowed × 1000 ÷ (2 or √3 × R × I) L one-way length, ft R Ω per 1000 ft, Chapter 9 Table 8 I load current, A system voltage line-to-line for three-phase
Single-phase, an example, not a recommendation: a 120 V branch circuit in 12 AWG copper (1.98 Ω/1000 ft) run 100 ft to a 16 A load drops 2 × 100 × 1.98 × 16 ÷ 1000 = 6.34 V, which is 5.28% of 120 V, leaving 113.66 V at the load.
Three-phase: a 208 V feeder in 1/0 AWG copper (0.122 Ω/1000 ft) run 200 ft at 120 A drops √3 × 200 × 0.122 × 120 ÷ 1000 = 5.07 V, or 2.44%.
On AC, large conductors also have reactance. The Chapter 9 Table 9 impedance method, which depends on the power factor and whether the raceway is steel, PVC or aluminum, gives a somewhat higher drop for them, so check a large feeder that lands close to your target with Table 9.
One-way length or round trip?
Enter the one-way length, from the panel to the load as you'd measure it on the drawings. The 2 in the single-phase formula is the return conductor: current goes out on one wire and back on the other, so the drop is over twice the run. Three-phase uses √3, which turns the drop on one conductor into the drop in the line-to-line voltage. Entering the round trip doubles the answer.
When should you upsize the wire for voltage drop?
When the drop runs past your target. Informational notes to 210.19(A) and 215.2(A) suggest no more than 3% on a branch circuit or a feeder and 5% for the two combined; they are guidance, not requirements, though a specification, an energy code or the authority having jurisdiction can make a limit mandatory. A larger conductor has less resistance: the example's 12 AWG copper at 5.28% becomes 3.31% in 10 AWG copper. In Max distance mode, 12 AWG copper reaches 56 ft at 3% and 10 AWG copper 90 ft.
Upsizing the phase conductors for voltage drop upsizes the equipment grounding conductor too, in proportion to the circular mils (250.122(B)): the ground wire size calculator does that step. The conductor still needs its ampacity from Table 310.16: the wire size calculator checks ampacity, 240.4(D) and voltage drop together and picks the smallest size that passes all three.
A sizing aid, not the code. This calculator is based on NFPA 70, 2023 edition, Chapter 9 Table 8 (DC resistance at 75 °C, stranded conductors) and the informational notes to 210.19(A) and 215.2(A). It is not a substitute for the code, the engineer of record or the authority having jurisdiction. Local amendments, the edition your jurisdiction has adopted and conditions the calculator doesn't model (AC impedance and power factor, parallel sets, conductor temperatures other than 75 °C, motor starting) can change the answer.
Related tools
- Wire ampacity calculator: Get a conductor's allowable ampacity from NEC Table 310.16, derated for ambient and conductor count and capped at the 75 °C or 60 °C termination rating.
- Wire size calculator: Find the smallest wire for a load from NEC Table 310.16, with the 125% continuous-load factor, 240.4(D) breaker limits and an optional voltage-drop limit.
- Metric voltage drop calculator: Voltage drop in metres: type the cable's mV/A/m from its datasheet, the current, the length and the voltage for the drop in volts and percent, and a pass or fail against your own limit.
- Ground wire size calculator: Size the equipment grounding conductor from NEC Table 250.122, and upsize it in proportion when the phase conductors were upsized for voltage drop (250.122(B)).
- Neutral conductor size calculator: Size a feeder or service neutral from the NEC 220.61 unbalanced load, with the 70% reduction over 200 A, and the Table 250.122 or 250.102(C)(1) minimum.
- Motor circuit calculator: wire, breaker and ground size: Size a single motor's branch circuit from NEC Article 430: full-load current, the conductor at 125%, the largest breaker or fuse, the ground wire and the overload.
- Transformer amps calculator: Get a transformer's primary and secondary full-load amps from its kVA, phase and voltages, with a table for the standard kVA ratings.
- Ohm's law calculator: Enter any two of voltage, current, resistance and power to get the other two, with the formula used, for DC and resistive circuits.
- Conduit support spacing calculator: Get the NEC maximum distance between conduit supports and from a box for EMT, IMC, RMC, PVC, RTRC, ENT, FMC, LFMC and LFNC, and the minimum strap count for a run.
- Conduit fill and size calculator: What size conduit do you need? Mix wire types and sizes, grounds included, and get the smallest conduit that fits plus the fill % in every trade size, from NEC Chapter 9.
- Metric conduit fill calculator: Conduit fill in millimetres: type the conduit's internal diameter and each cable's overall diameter for the fill %, a pass or fail against your own limit and the largest cable that still fits.
- Fire alarm battery calculator: Size a fire alarm panel's standby battery in amp-hours from your devices' standby and alarm currents, the NFPA 72 standby and alarm times and a safety margin.
- Low-voltage cable footage calculator: Turn device counts into cable footage and 1,000 ft boxes: cables per device, average run and service loop per device type, plus waste, with a 295 ft check.
- Sleeve fill calculator: How many cables fit in a sleeve through a wall: the fill % against your firestop listing's max fill, the NEC 60% nipple and Table 1 figures for reference, and how many more cables fit.
- All free tools for electrical estimators
-
How do you calculate voltage drop?
Multiply 2 (single-phase) or √3 (three-phase) by the one-way length in feet, the conductor's resistance in ohms per 1000 ft from NEC Chapter 9 Table 8, and the load current, then divide by 1000. Divide the result by the system voltage for the percent. For 100 ft of 12 AWG copper at 16 A on 120 V single-phase, that is 6.34 V, or 5.28%.
-
What is the maximum voltage drop allowed by the NEC?
For most branch circuits and feeders, the NEC doesn't set a limit. Informational notes to 210.19(A) and 215.2(A) suggest sizing so the drop is no more than 3% on a branch circuit or a feeder, and no more than 5% on the feeder and branch circuit combined. Informational notes aren't enforceable requirements, though a specification, an energy code or the authority having jurisdiction may make them one. A few articles do set limits, for example for sensitive electronic equipment (647.4(D)).
-
Should I enter the one-way length or the round trip?
The one-way length, from the source to the load. The single-phase formula's 2 already counts the return conductor, and the three-phase formula's √3 turns the drop on one conductor into the drop in the line-to-line voltage. Entering the round trip would double the answer.
-
How far can I run a wire before voltage drop is a problem?
Switch the calculator to Max distance and enter your target drop. At 3%, 12 AWG copper carrying 16 A on 120 V single-phase reaches 56 ft one way, and 10 AWG copper reaches 90 ft. The answer scales with the voltage and inversely with the load: twice the current, half the distance.
-
Why does this give a lower drop than some other calculators?
This calculator uses the DC resistance at 75 °C from Chapter 9 Table 8, the method most estimators use for branch circuits and small feeders. On AC, large conductors also have reactance, and the Chapter 9 Table 9 impedance method (which depends on power factor and the raceway material) gives a somewhat higher drop for them. For large feeders where the drop is close to your target, check with Table 9 or ask the engineer of record.
-
If I upsize the wire for voltage drop, does the ground wire go up too?
Yes. When the ungrounded conductors are made larger than their ampacity requires, 250.122(B) increases a wire-type equipment grounding conductor in proportion to the increase in their circular mil area. The ground wire size calculator does that step.
-
Does this calculator save or send what I type?
No. The calculator runs entirely in your browser. Nothing you enter is saved or sent anywhere, and no account is needed.