Motor wire size calculator

A motor's branch circuit is sized from the table full-load current, not the nameplate: the wire at 125% of it, the breaker or fuse at up to the Table 430.52(C)(1) percentage, the ground wire from that device. A 25 HP, 460 V three-phase motor draws 34 A by Table 430.250, so it takes 8 AWG copper, up to a 90 A inverse-time breaker and 8 AWG copper for the ground.

Pick the motor, the wire and the device; add the nameplate current for the overload. Based on NFPA 70, 2023 edition, Article 430. It runs in your browser; nothing you type is saved or sent.

Example values, not benchmarks. Replace them with your own.

Motor

The ratings the table lists at that voltage.

Branch circuit

The lowest rating of the breaker, starter or motor lugs; 110.14(C).

For single-phase and squirrel-cage motors. A wound-rotor motor's limits are lower (Table 430.52(C)(1)) and aren't covered here.

Overload (optional)

From the motor's nameplate. Leave blank to skip the overload.

Branch-circuit conductor
8 AWG copper
Full-load current (Table 430.250)
34 A
Largest inverse-time breaker
90 A
Equipment ground
8 AWG copper
Overload, not more than
38.75 A
  • Sized from the table's full-load current, not the nameplate (430.6(A)(1)); the nameplate sets only the overload.
  • The breaker or fuse may be larger than the wire's ampacity: 240.4(G) sends motor circuits to Article 430, so 240.4(D) doesn't limit it. The overload protects the wire.

The working

FLC                = 34 A
  Table 430.250, 25 HP at 460 V; the table, not the nameplate (430.6(A)(1))

conductor ampacity = 34 A × 125% = 42.5 A
  430.22
conductor          = 8 AWG copper, 50 A at 75 °C
  Table 310.16, 75 °C termination column (110.14(C)), 86 °F, 3 or fewer CCC

max device         = 34 A × 250% = 85 A
  Table 430.52(C)(1), inverse-time breaker
next standard size = 90 A
  430.52(C)(1)(a), 240.6(A)

table EGC          = 8 AWG copper
  Table 250.122, 100 A row (device 90 A), 250.122(D)(1)

overload           = 31 A × 125% = 38.75 A
  430.32(A)(1), service factor 1.15 or more; nameplate current

Size the raceway: conduit fill calculator.

How do you size a motor branch circuit?

Five steps, each from its own section of Article 430. The full-load current comes from Table 430.248 (single-phase) or Table 430.250 (three-phase), never the nameplate (430.6(A)(1)). Everything else hangs off it, except the overload, which uses the nameplate.

FLC         = Table 430.248 / 430.250, by horsepower and voltage
conductor   = the smallest size with ampacity ≥ FLC × 125%       430.22
max device  = FLC × Table 430.52(C)(1) %, then the next standard
              size up when that isn't one                        430.52(C)(1)(a)
ground      = Table 250.122 at that device rating                250.122(D)(1)
overload    = nameplate FLA × 125% (SF ≥ 1.15 or rise ≤ 40 °C)
                          or × 115% (all other motors)            430.32(A)(1)

An example, not a recommendation: a 25 HP, 460 V three-phase motor is 34 A in Table 430.250. 34 A × 125% = 42.5 A, so 8 AWG copper (50 A in the 75 °C column). An inverse-time breaker may be 250%: 34 A × 250% = 85 A, not a standard size, so the next one up, 90 A. Table 250.122's 100 A row gives 8 AWG copper. With a 31 A nameplate and a 1.15 service factor, the overload trips at no more than 38.75 A.

What size breaker or fuse can a motor have?

Table 430.52(C)(1) gives the most each device may be, as a percent of the table full-load current. For single-phase motors and AC polyphase motors other than wound-rotor:

Table 430.52(C)(1) maximum rating or setting, percent of full-load current
Device Percent of full-load current
Inverse-time breaker 250%
Dual-element (time-delay) fuse 175%
Nontime-delay fuse 300%
Instantaneous-trip breaker 800% (1100% for Design B energy-efficient premium)

When the percentage doesn't land on a standard rating (240.6(A)), 430.52(C)(1)(a) allows the next standard size up. An instantaneous-trip breaker's figure is a maximum setting, and the breaker must be adjustable and part of a listed combination motor controller (430.52(C)(3)).

Three-phase motor full-load current chart (NEC Table 430.250)

Full-load current in amperes, three-phase AC induction-type squirrel-cage and wound-rotor motors, from NFPA 70, 2023 edition, Table 430.250. The voltages are rated motor voltages; the currents apply to system voltage ranges of 110–120, 220–240, 440–480 and 550–600 V. The calculator's motor is highlighted. Its breaker and fuse sizes are for squirrel-cage motors; a wound-rotor motor's Table 430.52(C)(1) limits are lower.

Table 430.250 three-phase motor full-load currents
HP 115 V200 V208 V230 V460 V575 V
1/2 4.42.52.42.21.10.9
3/4 6.43.73.53.21.61.3
1 8.44.84.64.22.11.7
1-1/2 126.96.6632.4
2 13.67.87.56.83.42.7
3 —1110.69.64.83.9
5 —17.516.715.27.66.1
7-1/2 —25.324.222119
10 —32.230.8281411
15 —48.346.2422117
20 —62.159.4542722
25 —78.274.8683427
30 —9288804032
40 —1201141045241
50 —1501431306552
60 —1771691547762
75 —2212111929677
100 —28527324812499
125 —359343312156125
150 —414396360180144
200 —552528480240192
250 ————302242
300 ————361289
350 ————414336
400 ————477382
450 ————515412
500 ————590472

Single-phase motor full-load current chart (NEC Table 430.248)

Full-load current in amperes, single-phase AC motors, from NFPA 70, 2023 edition, Table 430.248. The currents apply to system voltage ranges of 110–120 and 220–240 V.

Table 430.248 single-phase motor full-load currents
HP 115 V200 V208 V230 V
1/6 4.42.52.42.2
1/4 5.83.33.22.9
1/3 7.24.143.6
1/2 9.85.65.44.9
3/4 13.87.97.66.9
1 169.28.88
1-1/2 2011.51110
2 2413.813.212
3 3419.618.717
5 5632.230.828
7-1/2 80464440
10 10057.55550

A sizing aid, not the code. This calculator is based on NFPA 70, 2023 edition, Tables 430.248, 430.250, 430.52(C)(1), 310.16 and 250.122 and sections 430.6, 430.22, 430.32, 430.52 and 250.122. It is not a substitute for the code, the engineer of record or the authority having jurisdiction. Local amendments, the edition your jurisdiction has adopted and conditions the calculator doesn't model (ambient temperature, more than three current-carrying conductors, voltage drop, the 430.52(C)(1)(b) allowance for a motor that won't start, the motor and controller manufacturer's markings) can change the answer.

Related tools

  • Wire ampacity calculator: Get a conductor's allowable ampacity from NEC Table 310.16, derated for ambient and conductor count and capped at the 75 °C or 60 °C termination rating.
  • Wire size calculator: Find the smallest wire for a load from NEC Table 310.16, with the 125% continuous-load factor, 240.4(D) breaker limits and an optional voltage-drop limit.
  • Voltage drop calculator: Get a run's voltage drop in volts and percent from the NEC Chapter 9 Table 8 resistance, single- or three-phase, or the longest run that stays within a target drop.
  • Metric voltage drop calculator: Voltage drop in metres: type the cable's mV/A/m from its datasheet, the current, the length and the voltage for the drop in volts and percent, and a pass or fail against your own limit.
  • Ground wire size calculator: Size the equipment grounding conductor from NEC Table 250.122, and upsize it in proportion when the phase conductors were upsized for voltage drop (250.122(B)).
  • Neutral conductor size calculator: Size a feeder or service neutral from the NEC 220.61 unbalanced load, with the 70% reduction over 200 A, and the Table 250.122 or 250.102(C)(1) minimum.
  • Transformer amps calculator: Get a transformer's primary and secondary full-load amps from its kVA, phase and voltages, with a table for the standard kVA ratings.
  • Ohm's law calculator: Enter any two of voltage, current, resistance and power to get the other two, with the formula used, for DC and resistive circuits.
  • Conduit support spacing calculator: Get the NEC maximum distance between conduit supports and from a box for EMT, IMC, RMC, PVC, RTRC, ENT, FMC, LFMC and LFNC, and the minimum strap count for a run.
  • Conduit fill and size calculator: What size conduit do you need? Mix wire types and sizes, grounds included, and get the smallest conduit that fits plus the fill % in every trade size, from NEC Chapter 9.
  • Metric conduit fill calculator: Conduit fill in millimetres: type the conduit's internal diameter and each cable's overall diameter for the fill %, a pass or fail against your own limit and the largest cable that still fits.
  • Fire alarm battery calculator: Size a fire alarm panel's standby battery in amp-hours from your devices' standby and alarm currents, the NFPA 72 standby and alarm times and a safety margin.
  • Low-voltage cable footage calculator: Turn device counts into cable footage and 1,000 ft boxes: cables per device, average run and service loop per device type, plus waste, with a 295 ft check.
  • Sleeve fill calculator: How many cables fit in a sleeve through a wall: the fill % against your firestop listing's max fill, the NEC 60% nipple and Table 1 figures for reference, and how many more cables fit.
  • All free tools for electrical estimators

Questions

Frequently asked

Can't find an answer? Email contact@takeonbid.com — we read every one.

  • What size wire for a 25 HP, 460 V three-phase motor?

    Table 430.250 gives a full-load current of 34 A. 430.22 sizes the branch-circuit conductors at 125% of it, 42.5 A, which takes 8 AWG copper (50 A at 75 °C in Table 310.16). The largest inverse-time breaker is 90 A and the equipment grounding conductor 8 AWG copper.

  • What size breaker for a 10 HP, 230 V three-phase motor?

    Up to 70 A inverse-time. Table 430.250 gives 28 A, and Table 430.52(C)(1) allows 250% of it for an inverse-time breaker, 70 A. When that isn't a standard size, 430.52(C)(1)(a) allows the next standard rating up. The conductors are 10 AWG copper, from 125% of the full-load current.

  • Why can the motor breaker be bigger than the wire's ampacity?

    Because the breaker or fuse on a motor branch circuit only protects against short circuits and ground faults; the overload relay protects the wire and the motor from overload. 240.4(G) sends motor circuits to Article 430, so the 240.4(D) small-conductor limits don't apply: a 1 HP, 115 V single-phase motor on 14 AWG copper (16 A full-load) may have up to a 40 A inverse-time breaker.

  • Do I use the nameplate amps or the table amps?

    The table. 430.6(A)(1) sizes the conductors, the short-circuit and ground-fault protection and the ampacity of switches from the full-load current in Tables 430.247 through 430.250, not the nameplate. The nameplate current is used for the separate overload protection (430.6(A)(2), 430.32).

  • How do you size motor overload protection?

    430.32(A)(1): a separate overload device rated or set to trip at no more than 125% of the nameplate full-load current for a motor marked with a service factor of 1.15 or more or a temperature rise of 40 °C or less, and 115% for all other motors. With a 31 A nameplate that's 38.75 A or 35.65 A. If that isn't enough to start the motor, 430.32(C) allows up to 140% and 130%; this calculator doesn't apply that step.

  • What size ground wire does a motor circuit need?

    250.122(D)(1): from Table 250.122 at the rating of the motor branch-circuit short-circuit and ground-fault device. For an instantaneous-trip breaker it's sized from the largest dual-element time-delay fuse 430.52(C)(1)(a) would allow instead: for the 25 HP, 460 V example that's a 60 A fuse and 10 AWG copper. 250.122(A) never requires it to be larger than the circuit conductors.

  • Does this cover several motors on a feeder, VFDs or air conditioners?

    No. It sizes a single motor on its own branch circuit. Feeders serving several motors (430.24, 430.62), motors fed from an adjustable-speed drive (430.122), hermetic refrigerant motor-compressors (Article 440), DC, synchronous and wound-rotor motors, and medium-voltage motors are out of scope. It gives no starter size or heater, which are manufacturer-specific.