Conduit fill and size calculator

Conduit fill is the conductors' total cross-section area divided by the conduit's internal area. The NEC allows 40% for three or more conductors, 31% for two and 53% for one (Chapter 9, Table 1).

To size conduit, pick a conduit type and add a row for each kind of conductor, grounds included. The calculator gives the smallest trade size that fits, which is the conduit size you need, and the fill in every size. It runs in your browser; nothing you type is saved or sent.

Working in millimeters, or not to the NEC? Use the metric conduit fill calculator, with your own diameters and limit.

Example values, not benchmarks. Replace them with your own.

Conduit
Conductors — one row per kind

Count every conductor, grounds included. A multiconductor cable counts as one conductor: pick "Other cable" and enter its outside diameter.

Smallest conduit that fits
¾″ EMT
Conductors
4
Conductor area
0.1309 in²

Fill limit: 3 or more conductors → 40% (NEC Chapter 9, Table 1).

Fill in every trade size of the chosen conduit type
Trade size Area (in²) Fill Fits?
½″ 0.304 43.1% No
¾″ 0.533 24.6% Yes
1″ 0.864 15.2% Yes
1¼″ 1.496 8.8% Yes
1½″ 2.036 6.4% Yes
2″ 3.356 3.9% Yes
2½″ 5.858 2.2% Yes
3″ 8.846 1.5% Yes
3½″ 11.545 1.1% Yes
4″ 14.753 0.9% Yes

The formula, with your numbers

conductor area  = Σ count × area of one conductor
3 × #8 THHN     = 3 × 0.0366 = 0.1098 in²
1 × #10 THHN    = 1 × 0.0211 = 0.0211 in²
                = 0.1309 in²

fill %          = conductor area ÷ conduit area
¾″ EMT          = 0.1309 ÷ 0.533 = 24.6% (limit 40%)

What size conduit do I need?

The smallest trade size whose internal area (Chapter 9, Table 4) keeps the conductors within the Table 1 limit: 40% for three or more conductors, or a little over when all are the same size and Note 7 rounds the count up. For common circuits in EMT with THHN / THWN-2 copper, that's:

Smallest EMT trade size for 3, 4, 6 and 9 THHN conductors of #12 to #6, NEC 2023 Chapter 9
Conductors #12 THHN#10 THHN#8 THHN#6 THHN
3 ½″ 13.1% ½″ 20.8% ½″ 36.1% ¾″ 28.5%
4 ½″ 17.5% ½″ 27.8% ¾″ 27.5% ¾″ 38.0%
6 ½″ 26.3% ¾″ 23.8% ¾″ 41.2% · Note 7 1″ 35.2%
9 ½″ 39.4% ¾″ 35.6% 1″ 38.1% 1¼″ 30.5%

Each cell is the smallest EMT that fits and its fill. The count is every conductor in the conduit. An equipment ground counts too (Note 3) but is often a smaller size, so add it as its own row in the calculator. Select a size to open that case in the calculator, then change the conduit type or add rows. A cell marked Note 7 fits by Chapter 9, Note 7: with all conductors the same size, the most a conduit holds is rounded up when its decimal is 0.8 or more, so its fill can read a little over 40%. 6 #8 THHN in ¾″ EMT is 41.2% full, but it holds 40% × 0.533 ÷ 0.0366 = 5.83, which rounds up to 6. Annex C, Table C.1 lists the same.

How do you calculate conduit fill?

Add up the area of every conductor, then divide by the conduit's internal area. The result has to stay within the Table 1 limit for the number of conductors, unless every conductor (or every cable, entered by its OD) is the same size and Note 7's round-up allows one more.

conductor area = Σ count × area of one conductor   (Table 5 or Table 8)
fill %         = conductor area ÷ conduit area    (Table 4)
fits           = fill % ≤ limit                   (Table 1: 53%, 31% or 40%)
               or, all one size (or one OD) and 3 or more:
               count ≤ limit × conduit area ÷ one conductor's area,
                       rounded up at a decimal of 0.8 or more    (Note 7)

What size conduit for 3 × #8 THHN + 1 × #10 THHN?

This is an example run, the calculator's starting values: 3 × #8 THHN + 1 × #10 THHN in EMT. That's 4 conductors, so the limit is 40%.

conductor area  = Σ count × area of one conductor
3 × #8 THHN     = 3 × 0.0366 = 0.1098 in²
1 × #10 THHN    = 1 × 0.0211 = 0.0211 in²
                = 0.1309 in²

fill %          = conductor area ÷ conduit area
¾″ EMT          = 0.1309 ÷ 0.533 = 24.6% (limit 40%)

½″ EMT has 0.304 in² inside, so 40% of it is 0.1216 in², less than the conductors' 0.1309 in². It would be 43.1% full. ¾″ EMT (0.533 in²) holds them at 24.6%, so ¾″ EMT is the smallest that fits.

How do the NEC fill rules work?

  • The limit depends on how many conductors there are (Table 1): 53% for one, 31% for two, 40% for three or more. Count every conductor in the conduit.
  • Grounds count (Note 3). An equipment grounding or bonding conductor is included at its actual size, insulated or bare.
  • A multiconductor cable counts as one conductor (Note 9), at its outside diameter. The calculator works out its area as π/4 × OD².
  • Mixed sizes are added up by area (Note 6): each conductor's area from Table 5 or Table 8, the conduit's from Table 4.
  • All one size rounds up at 0.8 (Note 7). When every conductor is the same type and size, or every row is an "Other cable" of the same OD, the most that fit is the limit's area divided by one conductor's area, and a decimal of 0.8 or more rounds up to the next whole conductor. Annex C's tables are built this way. The calculator applies it at three or more conductors and marks a size that fits only by it. Mixed sizes, and "Other cable" rows mixed with table rows or with another OD, are held to the plain limit.

The calculator checks fill only. Pulling tension, the number of bends between pull points, and ampacity adjustment for more than three current-carrying conductors are separate rules. If you measure conduit runs off a PDF, our guides to measuring conduit homeruns and counting fittings along a run cover the takeoff side.

Sources. Based on NFPA 70 (NEC), 2023 edition: conduit areas from Chapter 9, Table 4; conductor areas from Table 5 (insulated) and Table 8 (bare); fill limits from Table 1, with Note 7's round-up for conductors or cables all of one size. This is a sizing aid, not a substitute for the code, the engineer of record or the authority having jurisdiction. Local amendments and conditions the calculator doesn't model can change the answer; for a cable not in the tables, use the manufacturer's outside diameter.

Related tools

  • Conduit support spacing calculator: Get the NEC maximum distance between conduit supports and from a box for EMT, IMC, RMC, PVC, RTRC, ENT, FMC, LFMC and LFNC, and the minimum strap count for a run.
  • Metric conduit fill calculator: Conduit fill in millimetres: type the conduit's internal diameter and each cable's overall diameter for the fill %, a pass or fail against your own limit and the largest cable that still fits.
  • Wire ampacity calculator: Get a conductor's allowable ampacity from NEC Table 310.16, derated for ambient and conductor count and capped at the 75 °C or 60 °C termination rating.
  • Wire size calculator: Find the smallest wire for a load from NEC Table 310.16, with the 125% continuous-load factor, 240.4(D) breaker limits and an optional voltage-drop limit.
  • Voltage drop calculator: Get a run's voltage drop in volts and percent from the NEC Chapter 9 Table 8 resistance, single- or three-phase, or the longest run that stays within a target drop.
  • Metric voltage drop calculator: Voltage drop in metres: type the cable's mV/A/m from its datasheet, the current, the length and the voltage for the drop in volts and percent, and a pass or fail against your own limit.
  • Ground wire size calculator: Size the equipment grounding conductor from NEC Table 250.122, and upsize it in proportion when the phase conductors were upsized for voltage drop (250.122(B)).
  • Neutral conductor size calculator: Size a feeder or service neutral from the NEC 220.61 unbalanced load, with the 70% reduction over 200 A, and the Table 250.122 or 250.102(C)(1) minimum.
  • Motor circuit calculator: wire, breaker and ground size: Size a single motor's branch circuit from NEC Article 430: full-load current, the conductor at 125%, the largest breaker or fuse, the ground wire and the overload.
  • Transformer amps calculator: Get a transformer's primary and secondary full-load amps from its kVA, phase and voltages, with a table for the standard kVA ratings.
  • Ohm's law calculator: Enter any two of voltage, current, resistance and power to get the other two, with the formula used, for DC and resistive circuits.
  • Fire alarm battery calculator: Size a fire alarm panel's standby battery in amp-hours from your devices' standby and alarm currents, the NFPA 72 standby and alarm times and a safety margin.
  • Low-voltage cable footage calculator: Turn device counts into cable footage and 1,000 ft boxes: cables per device, average run and service loop per device type, plus waste, with a 295 ft check.
  • Sleeve fill calculator: How many cables fit in a sleeve through a wall: the fill % against your firestop listing's max fill, the NEC 60% nipple and Table 1 figures for reference, and how many more cables fit.
  • All free tools for electrical estimators

Questions

Frequently asked

Can't find an answer? Email contact@takeonbid.com — we read every one.

  • What is the maximum conduit fill allowed by the NEC?

    40% of the conduit's internal area for three or more conductors, the usual case. NEC Chapter 9, Table 1 sets the limit by how many conductors there are: 53% for one, 31% for two, and 40% for three or more. The internal areas for each conduit type and trade size are in Chapter 9, Table 4.

  • What does 40% conduit fill mean?

    It means the conductors may take up no more than 40% of the conduit's internal cross-sectional area: the NEC Chapter 9, Table 1 limit for three or more conductors (one conductor may fill 53%, two 31%). For example, ½″ EMT has 0.304 in² inside (Table 4), so three or more conductors in it may total 0.1216 in²; 9 #12 THHN at 0.0133 in² each take 0.1197 in², 39.4%. The other 60% stays empty, which leaves room to pull the conductors in.

  • What is a good conduit fill percentage?

    Any fill at or under the NEC Chapter 9, Table 1 limit is allowed: 40% for three or more conductors, 31% for two and 53% for one. The limit is a maximum, not a target, so a fill well under it is fine, and a long pull or a run with several bends goes in more easily with room to spare. Fill is a separate check from ampacity: more than three current-carrying conductors in one raceway also need the adjustment factors in 310.15(C)(1).

  • How do you calculate conduit fill?

    Divide the conductors' total area by the conduit's internal area, then check the result against the Chapter 9, Table 1 limit (40% for three or more conductors). Take the area of one conductor from Table 5 (insulated) or Table 8 (bare), multiply it by the count and add every row, then divide by the trade size's area from Table 4. For example, 4 #10 THHN take 4 × 0.0211 = 0.0844 in², and 0.0844 ÷ 0.304 in² of ½″ EMT is 27.8%, under the 40% limit.

  • Do ground wires count toward conduit fill?

    Yes. Chapter 9, Note 3 says equipment grounding and bonding conductors, where installed, are included when you calculate conduit fill, at their actual dimensions, insulated or bare. Add the ground as its own row in the calculator; it also counts toward the 1 / 2 / 3-or-more conductor limit.

  • How do I count a multiconductor cable in conduit fill?

    Chapter 9, Note 9 treats a multiconductor cable as a single conductor. Use the cable's outside diameter from the manufacturer's data: in the calculator, pick "Other cable" and enter the OD, with a count of 1 per cable. For an elliptical cable, the note says to use the major diameter.

  • How do I size conduit for different wire sizes?

    Use the smallest trade size whose internal area keeps the conductors within the Chapter 9, Table 1 limit (40% for three or more conductors; with every conductor the same size, Note 7 rounds the count up at a decimal of 0.8 or more). Look up the area of one conductor of each type and size in Table 5 (insulated) or Table 8 (bare), multiply each by its count and add them up (Note 6), then compare the total with each trade size's area from Table 4. For example, 3 #8 THHN and 1 #10 THHN total 0.1309 in², which fits ¾″ EMT at 24.6%. The calculator does this for every row and every trade size at once.

  • What size conduit for 3 #10 THHN?

    ½″ EMT. Three #10 THHN take 0.0633 in², 20.8% of ½″ EMT against the 40% limit (Chapter 9, Table 1). With a #10 ground added it is still ½″ EMT (27.8%). PVC Schedule 40 needs ½″ PVC Sch 40.

  • What size conduit for 4 #6 THHN plus a #10 ground?

    1″ EMT. The five conductors, ground included (Chapter 9, Note 3), take 0.2239 in², which is 25.9% of 1″ EMT. ¾″ EMT would be 42.0% full, over the 40% limit.

  • What size conduit for 4 #3/0 THHN and a #6 ground?

    2″ EMT (33.4% full). In PVC Schedule 40 it is 2″ PVC Sch 40 (34.1%). Table 5 gives one area per insulation type and size, so standard (non-compact) aluminum THHN sizes the same as copper.

  • How many #12 THHN fit in ½″ EMT?

    9 in all, counting any ground among them. At 9 the fill is 39.4%; one more makes 43.8%, over the 40% limit for 3 or more conductors (Chapter 9, Table 1). ¾″ EMT holds 16 #12 THHN, and ½″ EMT holds 5 #10 THHN.

  • How many #12 THHN fit in 1″ EMT?

    26 in all, counting any ground among them. At 26 the fill is 40.1% (over 40%, allowed by Chapter 9, Note 7's round-up for conductors all of one size); one more makes 41.6%, over the 40% limit for 3 or more conductors (Chapter 9, Table 1). 1″ EMT holds 16 #10 THHN.

  • How many wires can I put in a 2 inch conduit?

    101 #12 THHN in 2″ EMT, or 63 #10 THHN, when every wire is the same size and the grounds are counted among them. At 101 the fill is 40.1% (over 40%, allowed by Chapter 9, Note 7's round-up for conductors all of one size); one more makes 40.4%, over the 40% limit for 3 or more conductors (Chapter 9, Table 1). Other conduit types and wire sizes hold different counts, so enter yours in the calculator.

  • Does the calculator use the 60% fill for short nipples?

    No. Chapter 9, Note 4 allows a nipple of 24 inches or less between boxes or enclosures to be filled to 60%. This calculator doesn't apply the nipple allowance: it uses the Table 1 limits (with Note 7's round-up for conductors or cables all of one size). For cables through a wall sleeve, the sleeve fill calculator checks the fill against your firestop listing's maximum instead.

  • Can I use it for compact aluminum conductors?

    Not from the dropdown. Compact conductors have their own dimensions in Chapter 9, Table 5A, which this calculator doesn't include. Enter the conductor's outside diameter as an "Other cable" row instead.

  • Does this calculator save or send what I type?

    No. The calculator runs entirely in your browser. Nothing you enter is saved or sent anywhere, and no account is needed.