Wire ampacity calculator

A conductor's allowable ampacity is its Table 310.16 value in its insulation's column, derated for ambient temperature and the number of current-carrying conductors, and then capped at the column of the terminations it lands on. 12 AWG copper THHN reads 30 A in the 90 °C column, but on 75 °C terminations it is limited to 25 A, and 240.4(D) caps its breaker at 20 A.

Pick the conductor and the termination rating; open "Adjust for conditions" for a hot room or a full raceway. Based on NFPA 70, 2023 edition. It runs in your browser; nothing you type is saved or sent.

Example values, not benchmarks. Replace them with your own.

Conductor

Aluminum starts at 12 AWG in Table 310.16.

The column the conductor is derated from. THWN‑2 and RHW‑2 are 90 °C too.

The lowest rating of the breaker, lug or device at either end; 110.14(C).

Allowable ampacity
25 A
Adjusted for conditions
30 A
Termination limit (75 °C)
25 A

The 75 °C termination limit governs.

The working

base ampacity      = 30 A
  Table 310.16, 90 °C column, 12 AWG copper
× ambient factor   × 1.00
  Table 310.15(B)(1)(1), 86 °F (78–86 °F row)
× conductor count  × 1.00
  Table 310.15(C)(1), 3 current-carrying conductors
= adjusted         = 30 A

termination limit  = 25 A
  Table 310.16, 75 °C column, 110.14(C)

allowable          = 25 A
  the lower of the two: termination limit governs

How do you calculate allowable ampacity?

Take the Table 310.16 value in the insulation's temperature column, multiply by the ambient correction factor and the conductor-count adjustment factor, then compare it with the value in the termination's column. The lower of the two is the allowable ampacity.

adjusted    = Table 310.16 (insulation column)
              × ambient factor   (Table 310.15(B)(1)(1))
              × count factor     (Table 310.15(C)(1))
termination = Table 310.16 (termination column, 110.14(C))
allowable   = the lower of adjusted and termination

The ambient factor is 1.00 at 78–86 °F and falls as the room gets hotter; the count factor is 1.00 for up to three current-carrying conductors, 0.80 for four to six, and lower from there.

Why is 90 °C wire limited by a 75 °C lug?

A breaker or lug is only tested to run at its own rating. 110.14(C) lets a 90 °C conductor use its 90 °C ampacity as the base for derating, so it loses less to heat and crowding, but what it ends up carrying can't exceed the ampacity in the termination's column.

An example, not a recommendation: 12 AWG copper THHN with three current-carrying conductors at 86 °F derates nothing, so the 30 A from the 90 °C column is capped at 25 A by 75 °C terminations. Put six current-carrying conductors in the raceway and the derating governs instead: 30 A × 0.80 = 24 A, under the 25 A limit. Reading the 75 °C column first and derating that (25 A × 0.80 = 20 A) would undersize the conductor's ampacity for no reason; reading the 90 °C column and stopping there would overload the lug.

Why is the breaker smaller than the ampacity on small wire?

240.4(D) sets the most overcurrent protection 14, 12 and 10 AWG conductors may have, whatever the ampacity tables say: 15, 20 and 30 A for copper, and 15 and 25 A for 12 and 10 AWG aluminum. So 12 AWG copper with an allowable ampacity of 25 A still goes on a 20 A breaker. The calculator shows this limit as the max breaker for those sizes.

Wire ampacity chart (NEC Table 310.16)

Allowable ampacities of insulated conductors rated up to 2000 volts, not more than three current-carrying conductors in a raceway, cable or earth, at an ambient of 30 °C (86 °F). From NFPA 70, 2023 edition, Table 310.16. The calculator's size and insulation are highlighted.

Aluminum includes copper-clad aluminum. Table 310.16 lists no 14 AWG aluminum. Correction for ambient temperature (Table 310.15(B)(1)(1)) runs from 50 or less °F to 177–185 °F.

A sizing aid, not the code. This calculator is based on NFPA 70, 2023 edition, Tables 310.16, 310.15(B)(1)(1) and 310.15(C)(1) and sections 110.14(C) and 240.4(D). It is not a substitute for the code, the engineer of record or the authority having jurisdiction. Local amendments, the edition your jurisdiction has adopted and conditions the calculator doesn't model can change the answer.

Related tools

  • Wire size calculator: Find the smallest wire for a load from NEC Table 310.16, with the 125% continuous-load factor, 240.4(D) breaker limits and an optional voltage-drop limit.
  • Voltage drop calculator: Get a run's voltage drop in volts and percent from the NEC Chapter 9 Table 8 resistance, single- or three-phase, or the longest run that stays within a target drop.
  • Metric voltage drop calculator: Voltage drop in metres: type the cable's mV/A/m from its datasheet, the current, the length and the voltage for the drop in volts and percent, and a pass or fail against your own limit.
  • Ground wire size calculator: Size the equipment grounding conductor from NEC Table 250.122, and upsize it in proportion when the phase conductors were upsized for voltage drop (250.122(B)).
  • Neutral conductor size calculator: Size a feeder or service neutral from the NEC 220.61 unbalanced load, with the 70% reduction over 200 A, and the Table 250.122 or 250.102(C)(1) minimum.
  • Motor circuit calculator: wire, breaker and ground size: Size a single motor's branch circuit from NEC Article 430: full-load current, the conductor at 125%, the largest breaker or fuse, the ground wire and the overload.
  • Transformer amps calculator: Get a transformer's primary and secondary full-load amps from its kVA, phase and voltages, with a table for the standard kVA ratings.
  • Ohm's law calculator: Enter any two of voltage, current, resistance and power to get the other two, with the formula used, for DC and resistive circuits.
  • Conduit support spacing calculator: Get the NEC maximum distance between conduit supports and from a box for EMT, IMC, RMC, PVC, RTRC, ENT, FMC, LFMC and LFNC, and the minimum strap count for a run.
  • Conduit fill and size calculator: What size conduit do you need? Mix wire types and sizes, grounds included, and get the smallest conduit that fits plus the fill % in every trade size, from NEC Chapter 9.
  • Metric conduit fill calculator: Conduit fill in millimetres: type the conduit's internal diameter and each cable's overall diameter for the fill %, a pass or fail against your own limit and the largest cable that still fits.
  • Fire alarm battery calculator: Size a fire alarm panel's standby battery in amp-hours from your devices' standby and alarm currents, the NFPA 72 standby and alarm times and a safety margin.
  • Low-voltage cable footage calculator: Turn device counts into cable footage and 1,000 ft boxes: cables per device, average run and service loop per device type, plus waste, with a 295 ft check.
  • Sleeve fill calculator: How many cables fit in a sleeve through a wall: the fill % against your firestop listing's max fill, the NEC 60% nipple and Table 1 figures for reference, and how many more cables fit.
  • All free tools for electrical estimators
  • The 90 °C column and 75 °C lugs, with worked examples: can you use the 90 °C column for THHN wire?

Questions

Frequently asked

Can't find an answer? Email contact@takeonbid.com — we read every one.

  • What is ampacity?

    Ampacity is the maximum current, in amperes, a conductor can carry continuously under the conditions of use without exceeding its temperature rating (NEC Article 100). Table 310.16 gives it for up to three current-carrying conductors at a 30 °C (86 °F) ambient; hotter rooms and fuller raceways lower it.

  • Can I use the 90 °C column for THHN wire?

    Only as the starting point for derating. 110.14(C) lets a conductor with a higher rating than its terminations use that higher column for ambient correction and conductor-count adjustment, but the result can't exceed the ampacity in the termination's column. 12 AWG copper THHN reads 30 A at 90 °C, but on 75 °C terminations it is limited to 25 A.

  • What termination rating should I use?

    The lowest temperature rating of the breaker, lug or device at either end of the conductor, from its listing or marking. 110.14(C)(1) also sets defaults where the equipment isn't marked: 60 °C for circuits of 100 A or less or 14 through 1 AWG conductors, unless the equipment is listed and identified for higher-rated conductors, and 75 °C above 100 A or for conductors larger than 1 AWG.

  • Why is the max breaker for 12 AWG copper 20 A when its ampacity is 25 A?

    240.4(D) caps the overcurrent protection for small conductors regardless of the ampacity tables: 15 A for 14 AWG copper, 20 A for 12 AWG copper and 30 A for 10 AWG copper; 15 A for 12 AWG aluminum and 25 A for 10 AWG aluminum. Some circuits, such as motor circuits, are covered by 240.4(G) and follow their own articles instead.

  • Which conductors count as current-carrying?

    Every ungrounded (hot) conductor counts. Whether a neutral counts depends on the circuit: 310.15(E) covers it, for example a neutral carrying only the unbalanced current of a balanced circuit doesn't count, while one on a 4-wire wye circuit feeding mostly nonlinear loads does. Equipment grounding and bonding conductors don't count (310.15(F)). Enter the count; the calculator applies Table 310.15(C)(1).

  • Does this calculator cover conductors in free air or cable tray?

    No. It uses Table 310.16, for up to three current-carrying conductors in a raceway, cable or earth, rated up to 2000 volts. Single conductors in free air (Table 310.17), cable tray and medium-voltage cables use other tables.

  • Does this calculator save or send what I type?

    No. The calculator runs entirely in your browser. Nothing you enter is saved or sent anywhere, and no account is needed.