Can you use the 90 °C column for THHN wire?

Yes, but only to derate from. NEC 110.14(C) caps THHN at its terminations' column, 60 °C or 75 °C; the 90 °C ampacity is where hot-room and fill derating start.

The TakeOn Team 5 min read

A calculator card with labelled inputs for load, material, insulation and length, and a blank result

In short: Yes, you can use the 90 °C column for THHN, but only as the number you derate from. NEC 110.14(C) lets a 90 °C conductor apply the ambient and conductor-count factors of 310.15 to its 90 °C ampacity, then caps the result at the ampacity in the column of the lowest-rated termination it lands on, which is almost always 75 °C or 60 °C. You get the lower of the two.

Key takeaways

  • THHN is 90 °C in dry and damp locations (Table 310.4(1)), so its Table 310.16 value comes from the 90 °C column.
  • A conductor can’t be loaded past the rating of the breaker, lug or device at either end (110.14(C)).
  • Circuits of 100 A or less, or conductors 14 through 1 AWG, default to the 60 °C column unless the equipment is listed for more (110.14(C)(1)(a)); larger ones to 75 °C (110.14(C)(1)(b)).
  • The 90 °C column pays off once you derate: a hot room or a full raceway starts from a bigger number, and the 90 °C ambient factors are milder, so more is left after the derate.

All code references here are to the 2023 NEC, the edition our wire ampacity calculator uses. It runs the same two checks this post walks through.

What does the 90 °C rating on THHN mean?

The 90 °C rating on THHN is the highest temperature its insulation is listed to run at continuously, and Table 310.16 gives the current that holds a conductor to that temperature at a 30 °C (86 °F) ambient with no more than three current-carrying conductors. THHN gets that rating only in dry and damp locations. In a wet location, the marking decides: THHN/THWN dual-rated wire is 75 °C wet, and THWN-2 is 90 °C wet (Table 310.4(1)).

The wire is only half the circuit. Every conductor ends at a breaker, a lug or a device terminal, and those are tested at their own temperature. That is where 110.14(C) comes in.

Which column do the terminations allow?

The terminations allow the column of their own temperature rating: a conductor’s ampacity is limited to the lowest rating of any termination, conductor or device in the circuit (110.14(C)). Use the equipment’s marking or listing first. Where it doesn’t say, 110.14(C)(1) sets the default:

Circuit or conductorColumnSection
100 A or less, or 14 through 1 AWG60 °C, unless the equipment is listed and identified for higher-rated conductors110.14(C)(1)(a)
Over 100 A, or larger than 1 AWG75 °C110.14(C)(1)(b)

Many breakers and panelboards are marked 60/75 °C, which lets small circuits use the 75 °C column, but only when the conductor and every other termination on the circuit, such as the device at the far end, are rated 75 °C too. Check each marking; don’t assume it. 110.14(C)(1)(a) also has a provision for motors with design letters B, C or D, which may use 75 °C ampacity.

When does the 90 °C column actually help?

The 90 °C column helps when the conductor is derated, because the derating is applied to the bigger number. Two worked examples from the wire ampacity calculator, both 2/0 AWG copper THHN on 75 °C terminations (larger than 1 AWG, so 110.14(C)(1)(b) applies) in a 100 °F room:

Hot room, 3 conductorsHot room, 6 conductors
Base ampacity, 90 °C column (Table 310.16)195 A195 A
Ambient factor, 96–104 °F (Table 310.15(B)(1)(1))× 0.91× 0.91
Conductor-count factor (Table 310.15(C)(1))× 1.00× 0.80
Adjusted ampacity177.4 A141.9 A
Termination limit, 75 °C column175 A175 A
Allowable ampacity175 A, the lug governs141.9 A, the derating governs

The calculator rounds amps down to the tenth, never up: 195 × 0.91 = 177.45 A shows as 177.4 A, and 195 × 0.91 × 0.80 = 141.96 A as 141.9 A.

In the first case the hot room costs nothing. The derated 90 °C value is still above the 75 °C lug, so the conductor keeps its full 175 A. Had you started from the 75 °C column, its 96–104 °F factor of 0.88 would have taken it to 154 A.

In the second case the derating wins, and the lug no longer matters. Starting from 90 °C still leaves 141.9 A; the same conductor derated from the 75 °C column would be 123.2 A. Reading the 90 °C column and stopping there, at 195 A, would overload the lug in both cases.

Does the 60 °C rule still bite on small circuits?

Yes. On equipment held to 60 °C, a small THHN conductor carries well under its 90 °C value. From the same calculator, 6 AWG copper THHN reads 75 A in the 90 °C column:

  • On 60 °C terminations: 55 A, the 60 °C column.
  • On 75 °C terminations: 65 A.
  • On 60 °C terminations with six current-carrying conductors: 75 A × 0.80 = 60 A adjusted, still above 55 A, so the allowable stays 55 A.

That last line is the 90 °C column doing its job: the conductor took the derate without dropping below its termination limit. For 14, 12 and 10 AWG there is one more cap, the 240.4(D) limit on the breaker; that one is covered in why 12 AWG wire is rated 25 A but only on a 20 A breaker.

How do you check your own conductor?

You check your own conductor by entering its size, material, insulation and termination rating in the wire ampacity calculator and opening “Adjust for conditions” for the room temperature and the conductor count. It shows the adjusted value, the termination limit and which one governs. To start from the load instead, the wire size calculator picks the size. TakeOn measures the runs and counts on the PDF plans, so the conductor you size is the one you bid.

Try TakeOn free to measure your runs and counts from the plans.

Frequently asked questions

Is THHN wire rated 90 °C in a wet location?
No. Under NEC 2023 Table 310.4(1), THHN is a 90 °C insulation for dry and damp locations. Wire dual-marked THHN/THWN is 75 °C wet, and THWN-2 is 90 °C wet, so the column you derate from depends on the location as well as the marking.
Can a THHN conductor ever carry its full 90 °C ampacity?
Only where every termination, conductor and device it connects to is rated 90 °C, because NEC 2023 section 110.14(C) limits a conductor to the lowest temperature rating in the circuit. Breakers and panelboard lugs are typically marked 60 °C, 75 °C or 60/75 °C, so most THHN circuits are held to the 75 °C or 60 °C column.
Why derate THHN from the 90 °C column instead of the 75 °C column?
NEC 2023 section 110.14(C) lets a conductor rated higher than its terminations use its own higher rating for ambient correction and conductor-count adjustment. The 90 °C ampacity is larger and its ambient factors fall more slowly, so the derated result stays higher; it still can't exceed the ampacity in the termination's column.
What column applies to a 20 A or 60 A circuit with unmarked equipment?
The 60 °C column. NEC 2023 section 110.14(C)(1)(a) holds circuits rated 100 A or less, or conductors 14 through 1 AWG, to the 60 °C ampacity unless the equipment is listed and identified for higher-rated conductors. Above 100 A or larger than 1 AWG, 110.14(C)(1)(b) allows the 75 °C column.