Wire size calculator

The right wire size is the smallest conductor that passes every check: its allowable ampacity carries the load, 240.4(D) lets its breaker be that big, and the voltage drop stays within your limit. For a 20 A load run 100 ft at 120 V, ampacity alone allows 14 AWG copper, 240.4(D) needs 12 AWG, and a 3% drop limit needs 8 AWG.

Enter the load and the conductor; open the optional sections for a hot room, a full raceway, bundled cables or a voltage-drop limit. Based on NFPA 70, 2023 edition. It runs in your browser; nothing you type is saved or sent.

Sizing a cable? The conductors inside MC, SER or NM cable come from the same Table 310.16 lookup. NM cable (334.80), and SE or SER cable run through thermal insulation inside a building (338.10(B)(4)(a)), are held to the 60 °C column, though you may derate from their 90 °C rating: choose 90 °C insulation and a 60 °C termination rating.

Example values, not benchmarks. Replace them with your own.

Load

Tick it for a load expected to run 3 hours or more at a time: 210.19(A)(1) and 215.2(A)(1) size the conductor for 125% of it.

Conductor

The column the conductor is derated from.

The lowest rating of the breaker, lug or device at either end; 110.14(C).

Adjust for conditions

= 30 °C. The table is based on 86 °F (30 °C).

In the raceway or cable. Grounds never count.

Closed, the table's base conditions apply: 86 °F, three conductors.

Limit voltage drop

Line-to-line for three-phase.

Source to load, measured once.

3% is the informational-note guidance for one branch circuit or feeder.

Closed, voltage drop isn't checked.

Recommended size
8 AWG copper
Allowable ampacity
50 A
Voltage drop
2.59%

Ampacity needs 14 AWG; 240.4(D) needs 12 AWG; voltage drop needs 8 AWG → 8 AWG. Voltage drop governs.

CheckNeeds
Ampacity14 AWG
240.4(D)12 AWG
Voltage drop8 AWG

Upsize the ground wire too

Voltage drop took the conductors from 12 AWG to 8 AWG, 2.5283 times the circular mils. 250.122(B) increases a wire-type equipment grounding conductor in the same proportion: the ground wire size calculator does that step.

The working

design current  = 20 A (not continuous)

ampacity        → 14 AWG
  the smallest whose allowable ampacity is 20 A or more
  Table 310.16 90 °C column × 1.00 ambient × 1.00 count,
  capped at the 75 °C column (110.14(C))
240.4(D)        → 12 AWG
  the smallest whose max breaker is 20 A or more
voltage drop    → 8 AWG
  the smallest within 3% at 20 A over 100 ft one way
  VD = 2 × L × R × I ÷ 1000, R from Chapter 9 Table 8

recommended     = 8 AWG, the largest of the checks
  allowable ampacity 50 A
  drop 3.11 V = 2.59%, 116.89 V at the load

How do you size wire?

Work out the current the wire must carry, then find the smallest size that passes each check on its own. The largest of those sizes is the answer.

design current = load × 1.25 if continuous   (210.19(A)(1), 215.2(A)(1))
ampacity       = smallest size whose allowable ampacity ≥ design current
                 Table 310.16, × ambient and count factors,
                 capped at the termination column (110.14(C))
240.4(D)       = smallest size whose max breaker ≥ design current
                 (14 AWG Cu 15 A, 12 AWG Cu 20 A, 10 AWG Cu 30 A;
                  12 AWG Al 15 A, 10 AWG Al 25 A)
voltage drop   = smallest size whose drop ≤ the limit, at the load current
                 (Chapter 9 Table 8)
wire size      = the largest of the three

The ampacity step is the one the wire ampacity calculator shows in full, and the drop is the voltage drop calculator's. Picking the breaker itself (240.4, 240.6(A)) is a separate step: the calculator only makes sure 240.4(D) allows one large enough.

Why isn't 14 AWG enough for a 20 A load?

Its ampacity is: 14 AWG copper reads 20 A in the 75 °C column. But 240.4(D) caps its overcurrent protection at 15 A, and a 15 A breaker can't serve a 20 A load. So the calculator treats 240.4(D) as a check of its own, and 20 A gives 12 AWG copper. 240.4(G) circuits, such as motors, are exempt and follow their own articles; the motor circuit calculator sizes those.

How does a continuous load change the size?

A continuous load runs at its maximum for 3 hours or more, and the conductor is sized for 125% of it. An example, not a recommendation: a 13 A load needs 14 AWG copper as a noncontinuous load. Continuous, it's sized for 13 A × 1.25 = 16.25 A, which takes 12 AWG. The voltage-drop check still uses the 13 A that actually flows.

When does voltage drop decide the wire size?

On long runs. In the example, 10 AWG copper carries the 20 A easily but drops 4.96 V over 100 ft at 120 V, 4.13%: past the 3% limit. 8 AWG copper drops 3.11 V, 2.59%, so it's the size, with an allowable ampacity of 50 A.

Upsizing the conductors for voltage drop upsizes the ground wire too. Going from 12 AWG to 8 AWG is 2.5283 times the circular mils, and 250.122(B) increases a wire-type equipment grounding conductor in the same proportion. The ground wire size calculator does that step from the Table 250.122 size.

A sizing aid, not the code. This calculator is based on NFPA 70, 2023 edition, Tables 310.16, 310.15(B)(1)(1) and 310.15(C)(1), Chapter 9 Table 8 and sections 110.14(C), 210.19(A), 215.2(A), 240.4(D) and 250.122(B). It is not a substitute for the code, the engineer of record or the authority having jurisdiction. Local amendments, the edition your jurisdiction has adopted and conditions the calculator doesn't model can change the answer.

Related tools

  • Wire ampacity calculator: Get a conductor's allowable ampacity from NEC Table 310.16, derated for ambient and conductor count and capped at the 75 °C or 60 °C termination rating.
  • Voltage drop calculator: Get a run's voltage drop in volts and percent from the NEC Chapter 9 Table 8 resistance, single- or three-phase, or the longest run that stays within a target drop.
  • Metric voltage drop calculator: Voltage drop in metres: type the cable's mV/A/m from its datasheet, the current, the length and the voltage for the drop in volts and percent, and a pass or fail against your own limit.
  • Ground wire size calculator: Size the equipment grounding conductor from NEC Table 250.122, and upsize it in proportion when the phase conductors were upsized for voltage drop (250.122(B)).
  • Neutral conductor size calculator: Size a feeder or service neutral from the NEC 220.61 unbalanced load, with the 70% reduction over 200 A, and the Table 250.122 or 250.102(C)(1) minimum.
  • Motor circuit calculator: wire, breaker and ground size: Size a single motor's branch circuit from NEC Article 430: full-load current, the conductor at 125%, the largest breaker or fuse, the ground wire and the overload.
  • Transformer amps calculator: Get a transformer's primary and secondary full-load amps from its kVA, phase and voltages, with a table for the standard kVA ratings.
  • Ohm's law calculator: Enter any two of voltage, current, resistance and power to get the other two, with the formula used, for DC and resistive circuits.
  • Conduit support spacing calculator: Get the NEC maximum distance between conduit supports and from a box for EMT, IMC, RMC, PVC, RTRC, ENT, FMC, LFMC and LFNC, and the minimum strap count for a run.
  • Conduit fill and size calculator: What size conduit do you need? Mix wire types and sizes, grounds included, and get the smallest conduit that fits plus the fill % in every trade size, from NEC Chapter 9.
  • Metric conduit fill calculator: Conduit fill in millimetres: type the conduit's internal diameter and each cable's overall diameter for the fill %, a pass or fail against your own limit and the largest cable that still fits.
  • Fire alarm battery calculator: Size a fire alarm panel's standby battery in amp-hours from your devices' standby and alarm currents, the NFPA 72 standby and alarm times and a safety margin.
  • Low-voltage cable footage calculator: Turn device counts into cable footage and 1,000 ft boxes: cables per device, average run and service loop per device type, plus waste, with a 295 ft check.
  • Sleeve fill calculator: How many cables fit in a sleeve through a wall: the fill % against your firestop listing's max fill, the NEC 60% nipple and Table 1 figures for reference, and how many more cables fit.
  • All free tools for electrical estimators

Questions

Frequently asked

Can't find an answer? Email contact@takeonbid.com — we read every one.

  • How do you choose a wire size?

    Take the smallest conductor that passes every check: its allowable ampacity from Table 310.16 (derated for conditions, capped at the termination rating) carries the load, or 125% of it if it's continuous; 240.4(D) lets its breaker be that big; and, if you hold the run to a voltage drop, the drop is within the limit. For a 20 A load run 100 ft at 120 V, ampacity alone allows 14 AWG copper, 240.4(D) needs 12 AWG, and a 3% drop limit needs 8 AWG.

  • What size wire for a 20 amp circuit?

    12 AWG copper at the least, because 240.4(D) limits 14 AWG copper to a 15 A breaker even where its ampacity reads 20 A. For aluminum it's 10 AWG, which 240.4(D) limits to 25 A. A long run, a continuous load, a hot room or a full raceway can each call for a larger size; the calculator checks all of them.

  • What is a continuous load?

    A load where the maximum current is expected to continue for 3 hours or more (NEC Article 100). Branch-circuit and feeder conductors are sized for 125% of the continuous load plus 100% of the noncontinuous load (210.19(A)(1), 215.2(A)(1)). The calculator doesn't guess: tick the box when the load is continuous.

  • Does the NEC require upsizing for voltage drop?

    For most branch circuits and feeders, no. Informational notes to 210.19(A) and 215.2(A) suggest no more than 3% on a branch circuit or a feeder and 5% for both combined. They aren't enforceable requirements, though a specification, an energy code or the authority having jurisdiction may make them one. The calculator applies the limit only when you open its voltage-drop section.

  • Why does the ground wire get bigger when I upsize for voltage drop?

    250.122(B) says that when the ungrounded conductors are made larger than their ampacity requires, a wire-type equipment grounding conductor is increased in proportion to their circular mil area. The calculator shows that ratio whenever voltage drop set the size; the ground wire size calculator applies it to the Table 250.122 size.

  • Does this calculator size motor circuits or parallel conductors?

    No. Motor circuits are sized from the motor's full-load current under Article 430, and 240.4(G) exempts them from the 240.4(D) limits; the motor circuit calculator does that. Loads past what a single 2000 kcmil conductor carries need parallel sets, which this calculator doesn't size.

  • Is a cable size calculator the same as a wire size calculator?

    For the conductors, mostly. A cable such as MC, SER or NM is a set of insulated conductors in one jacket, and each conductor is sized from the same Table 310.16 lookup, with the same 125%, 240.4(D) and voltage-drop checks. Some cables add a limit: NM cable (334.80), and SE or SER cable run through thermal insulation inside a building (338.10(B)(4)(a)), are held to the 60 °C column, though you may derate from their 90 °C rating: choose 90 °C insulation and a 60 °C termination rating. Cables bundled or stacked together for more than 24 in. without spacing are adjusted under 310.15(C)(1) like conductors in a raceway: open Adjust for conditions and enter every current-carrying conductor in the bundle. For a 120/240 V dwelling service or main feeder, 310.12 lets the conductors be sized at 83% of the service rating; the calculator doesn't apply that, so its answer can be larger than 310.12 needs. The calculator sizes the conductors; it doesn't pick the cable type, its jacket or where the code allows it.

  • Does this work for BS 7671 or AS/NZS 3008?

    No. It uses the US National Electrical Code (NFPA 70, 2023) tables, which differ from BS 7671 and AS/NZS 3008 in their installation methods, current ratings, correction factors and voltage-drop limits. For a UK, Australian or New Zealand installation, use a calculator built on your local standard.

  • Does this calculator save or send what I type?

    No. The calculator runs entirely in your browser. Nothing you enter is saved or sent anywhere, and no account is needed.