Transformer amps calculator
A transformer's full-load amps is its kVA × 1000 divided by the voltage, and by √3 × the voltage for three-phase. A 75 kVA three-phase transformer is rated 90.2 A at 480 V on the primary and 208.2 A at 208 V on the secondary.
Enter the kVA, the phase and the line-to-line voltages, in kVA and volts. It runs in your browser; nothing you type is saved or sent.
How do you calculate transformer full-load amps?
Multiply the kVA by 1000 to get volt-amperes, then divide by the winding's line-to-line voltage. For three-phase, divide by √3 (about 1.732) as well. Work out each winding on its own: the kVA is the same on both sides, so the lower-voltage side carries the higher current.
single-phase I = kVA × 1000 ÷ V three-phase I = kVA × 1000 ÷ (√3 × V)
An example, not a recommendation: the same 75 kVA on a single-phase 208 V winding would carry 360.6 A, √3 times the 208.2 A of the three-phase one.
What protects the transformer and its secondary conductors?
Full-load amps is where sizing starts, not the answer. NEC 450.3 sets the transformer's overcurrent protection as a percentage of its rated current, and 240.21(C) sets the rules for the secondary conductors. Size those conductors from their ampacity: the wire size calculator finds the smallest conductor whose Table 310.16 ampacity carries the current.
Full-load amps for standard kVA ratings
Computed from the formula for the calculator's phase and voltages, rounded to the nearest tenth of an amp. Change the phase or voltages above and the table follows; the calculator's kVA is highlighted when it is one of these ratings.
| Rating | Primary (480 V) | Secondary (208 V) |
|---|---|---|
| 15 kVA | 18 A | 41.6 A |
| 30 kVA | 36.1 A | 83.3 A |
| 45 kVA | 54.1 A | 124.9 A |
| 75 kVA | 90.2 A | 208.2 A |
| 112.5 kVA | 135.3 A | 312.3 A |
| 150 kVA | 180.4 A | 416.4 A |
| 225 kVA | 270.6 A | 624.5 A |
| 300 kVA | 360.8 A | 832.7 A |
| 500 kVA | 601.4 A | 1,387.9 A |
| 750 kVA | 902.1 A | 2,081.8 A |
| 1,000 kVA | 1,202.8 A | 2,775.7 A |
A sizing aid, not the code. This calculator works out the rated current from the transformer's kVA and voltages. It doesn't size overcurrent protection under NFPA 70, 2023 edition, section 450.3, or the secondary conductors under 240.21(C), and it is not a substitute for the code, the engineer of record or the authority having jurisdiction. Local amendments and conditions the calculator doesn't model can change the answer.
Related tools
- Wire ampacity calculator: Get a conductor's allowable ampacity from NEC Table 310.16, derated for ambient and conductor count and capped at the 75 °C or 60 °C termination rating.
- Wire size calculator: Find the smallest wire for a load from NEC Table 310.16, with the 125% continuous-load factor, 240.4(D) breaker limits and an optional voltage-drop limit.
- Voltage drop calculator: Get a run's voltage drop in volts and percent from the NEC Chapter 9 Table 8 resistance, single- or three-phase, or the longest run that stays within a target drop.
- Metric voltage drop calculator: Voltage drop in metres: type the cable's mV/A/m from its datasheet, the current, the length and the voltage for the drop in volts and percent, and a pass or fail against your own limit.
- Ground wire size calculator: Size the equipment grounding conductor from NEC Table 250.122, and upsize it in proportion when the phase conductors were upsized for voltage drop (250.122(B)).
- Neutral conductor size calculator: Size a feeder or service neutral from the NEC 220.61 unbalanced load, with the 70% reduction over 200 A, and the Table 250.122 or 250.102(C)(1) minimum.
- Motor circuit calculator: wire, breaker and ground size: Size a single motor's branch circuit from NEC Article 430: full-load current, the conductor at 125%, the largest breaker or fuse, the ground wire and the overload.
- Ohm's law calculator: Enter any two of voltage, current, resistance and power to get the other two, with the formula used, for DC and resistive circuits.
- Conduit support spacing calculator: Get the NEC maximum distance between conduit supports and from a box for EMT, IMC, RMC, PVC, RTRC, ENT, FMC, LFMC and LFNC, and the minimum strap count for a run.
- Conduit fill and size calculator: What size conduit do you need? Mix wire types and sizes, grounds included, and get the smallest conduit that fits plus the fill % in every trade size, from NEC Chapter 9.
- Metric conduit fill calculator: Conduit fill in millimetres: type the conduit's internal diameter and each cable's overall diameter for the fill %, a pass or fail against your own limit and the largest cable that still fits.
- Fire alarm battery calculator: Size a fire alarm panel's standby battery in amp-hours from your devices' standby and alarm currents, the NFPA 72 standby and alarm times and a safety margin.
- Low-voltage cable footage calculator: Turn device counts into cable footage and 1,000 ft boxes: cables per device, average run and service loop per device type, plus waste, with a 295 ft check.
- Sleeve fill calculator: How many cables fit in a sleeve through a wall: the fill % against your firestop listing's max fill, the NEC 60% nipple and Table 1 figures for reference, and how many more cables fit.
- All free tools for electrical estimators
-
What are a transformer's full-load amps?
The current each winding carries when the transformer delivers its nameplate kVA. It's the kVA × 1000 divided by the voltage for single-phase, and by √3 × the voltage for three-phase. A 75 kVA three-phase transformer is rated 90.2 A at 480 V on the primary and 208.2 A at 208 V on the secondary.
-
Which voltage do I use for a 208Y/120 V or 120/240 V secondary?
The line-to-line voltage: 208 V for 208Y/120 V and 240 V for a 120/240 V single-phase three-wire secondary. The formulas take the voltage between the ungrounded conductors, not the voltage to neutral.
-
Is full-load amps the breaker size?
No. Full-load amps is the rated current. NEC 450.3 sets the maximum overcurrent protection for transformers as a percentage of the rated current, depending on the voltage, where the protection is and whether the secondary is protected too. This calculator gives the rated current; it doesn't size the breaker or fuse.
-
Why does three-phase divide by √3?
Three-phase power is √3 × the line-to-line voltage × the line current, because the three phases are 120° apart. Solving for the current gives kVA × 1000 ÷ (√3 × V); √3 is about 1.732.
-
Do I need the power factor?
No. A transformer is rated in kVA, which is apparent power, so the full-load current follows from the kVA and the voltage alone. The power factor matters when you start from a load in kW.
-
Does this calculator save or send what I type?
No. The calculator runs entirely in your browser. Nothing you enter is saved or sent anywhere, and no account is needed.
From the drawings to the bid
Count it, run it, price it.
TakeOn measures your devices and runs off the plans and turns them into a priced electrical bid. No credit card needed.