Sleeve fill calculator

Sleeve fill = the cables' total area ÷ the sleeve's internal area. A sleeve through a fire-rated wall is held to the maximum fill in its firestop system's listing, so that's the limit this calculator checks. You enter it; we don't supply listing values.

Pick the sleeve from the NEC Chapter 9 Table 4 sizes or type its internal diameter, then add your cables' outside diameters. You get the fill %, a pass or fail against the listing, and how many more cables fit. The NEC 60% and Table 1 figures are shown beside it for reference. It runs in your browser; nothing you type is saved or sent.

Example values, not benchmarks. Replace them with your own.

Sleeve

Picks the NEC reference figure: 60% up to 24 in, Table 1 past it.

Firestop listing

The maximum fill from your firestop system's listing. We don't supply listing values: read yours from the tested system you're installing.

Cables — one row per size
Area 1.1781 in²
Area 0.2827 in²

Enter each cable's outside diameter from its datasheet. The example diameters are made up. There are no built-in cable sizes.

Fill
43.5% · Enter your listing's max fill
More that fit the listing
—
Cables
28

NEC reference, not a verdict

Within 60% · more that fit: 7 more 0.3″ cables

24 in or shorter: Chapter 9, Note 4 (nipple) → 60%. Whether it applies to your sleeve is in the FAQ below.

More that fit counts extra cables the size of your largest one that keep the fill within the limit.

The formula, with your numbers

sleeve area = 3.3560 in² (2″ EMT, NEC Chapter 9 Table 4)
cable area  = 24 × π × 0.25² ÷ 4 + 4 × π × 0.3² ÷ 4 = 1.4608 in²
fill        = 1.4608 in² ÷ 3.3560 in² = 43.5%
listing: enter your firestop listing's max fill % to check it
NEC reference: within 60%; more that fit: 7 more 0.3″ cables (24 in or shorter: Chapter 9, Note 4 (nipple) → 60%)

How do you calculate sleeve fill?

Add up the cables' areas and divide by the sleeve's internal area:

cable area  = Σ count × π × OD² ÷ 4
sleeve area = Table 4's total area, or π × ID² ÷ 4
fill %      = cable area ÷ sleeve area

This is the calculator's example, not a benchmark. Its diameters are made up. 24 cables at 0.25″ OD and 4 cables at 0.3″ OD come to 1.4608 in². In a 2″ EMT sleeve (3.3560 in²), that's a fill of 43.5%. With no listing % entered, there's no verdict yet. Against the NEC's 60% reference figure for a short sleeve, 7 more 0.3″ cables would still fit.

Which limit applies to a sleeve through a wall?

Through a fire-rated wall or floor, the sleeve and its seal are a tested firestop system, and the system's listing states the maximum fill it was tested at. Fill past it and the penetration no longer matches the tested system. That's why the listing % is the calculator's pass or fail. Read it from the system you're installing.

The NEC figures are shown for reference (NFPA 70 (NEC), 2023 edition). Chapter 9, Note 4 lets a nipple of 24 inches or less between boxes, cabinets or similar enclosures be filled to 60%, and longer conduit uses the Table 1 limits: 53% for one cable, 31% for two and 40% for three or more. But Note 2 says Table 1 isn't meant for sections that only protect cable from physical damage, and communications, Class 2 and fire alarm cables have their own articles on when the Chapter 9 fill rules apply. Check yours, and ask the authority having jurisdiction.

For a conduit run with conductors, use the conduit fill and size calculator. The post on the 31% limit for two wires covers Notes 2 and 4 in more detail.

How many more cables fit?

The calculator adds cables the size of your largest one, one at a time, until the next one would pass the limit. It counts against the listing % and, separately, against the NEC reference figure. Past 24 inches the NEC figure changes with the count (53%, 31%, then 40%), so the count is checked at each step.

On a job, every sleeve is a count on the drawings. In a low-voltage takeoff in TakeOn, you count the penetrations and draw each cable run on the plans, so the bundle sizes come from the takeoff.

Related tools

  • Fire alarm battery calculator: Size a fire alarm panel's standby battery in amp-hours from your devices' standby and alarm currents, the NFPA 72 standby and alarm times and a safety margin.
  • Low-voltage cable footage calculator: Turn device counts into cable footage and 1,000 ft boxes: cables per device, average run and service loop per device type, plus waste, with a 295 ft check.
  • Wire ampacity calculator: Get a conductor's allowable ampacity from NEC Table 310.16, derated for ambient and conductor count and capped at the 75 °C or 60 °C termination rating.
  • Wire size calculator: Find the smallest wire for a load from NEC Table 310.16, with the 125% continuous-load factor, 240.4(D) breaker limits and an optional voltage-drop limit.
  • Voltage drop calculator: Get a run's voltage drop in volts and percent from the NEC Chapter 9 Table 8 resistance, single- or three-phase, or the longest run that stays within a target drop.
  • Metric voltage drop calculator: Voltage drop in metres: type the cable's mV/A/m from its datasheet, the current, the length and the voltage for the drop in volts and percent, and a pass or fail against your own limit.
  • Ground wire size calculator: Size the equipment grounding conductor from NEC Table 250.122, and upsize it in proportion when the phase conductors were upsized for voltage drop (250.122(B)).
  • Neutral conductor size calculator: Size a feeder or service neutral from the NEC 220.61 unbalanced load, with the 70% reduction over 200 A, and the Table 250.122 or 250.102(C)(1) minimum.
  • Motor circuit calculator: wire, breaker and ground size: Size a single motor's branch circuit from NEC Article 430: full-load current, the conductor at 125%, the largest breaker or fuse, the ground wire and the overload.
  • Transformer amps calculator: Get a transformer's primary and secondary full-load amps from its kVA, phase and voltages, with a table for the standard kVA ratings.
  • Ohm's law calculator: Enter any two of voltage, current, resistance and power to get the other two, with the formula used, for DC and resistive circuits.
  • Conduit support spacing calculator: Get the NEC maximum distance between conduit supports and from a box for EMT, IMC, RMC, PVC, RTRC, ENT, FMC, LFMC and LFNC, and the minimum strap count for a run.
  • Conduit fill and size calculator: What size conduit do you need? Mix wire types and sizes, grounds included, and get the smallest conduit that fits plus the fill % in every trade size, from NEC Chapter 9.
  • Metric conduit fill calculator: Conduit fill in millimetres: type the conduit's internal diameter and each cable's overall diameter for the fill %, a pass or fail against your own limit and the largest cable that still fits.
  • All free tools for electrical estimators
  • What goes into one: what is a low-voltage takeoff

Questions

Frequently asked

Can't find an answer? Email contact@takeonbid.com — we read every one.

  • How do you calculate sleeve fill?

    Work out each cable's cross-section area from its outside diameter (π × OD² ÷ 4), multiply by how many there are, and add the rows. Divide that by the sleeve's internal area: NEC Chapter 9 Table 4's total area for a conduit or tubing sleeve, or π × ID² ÷ 4 from its internal diameter. The answer is the fill %. Compare it with the maximum fill in your firestop system's listing.

  • What is the maximum fill for a firestop sleeve?

    Whatever the tested firestop system you're installing allows. A listed sleeve or penetration system states its own maximum fill, and it varies from one system to the next. Read it from that system's listing and enter it in the calculator. We don't publish listing values.

  • Does the NEC 60% nipple rule apply to a sleeve through a wall?

    Not usually. Chapter 9, Note 4 lets a nipple of 24 inches or less, installed between boxes, cabinets or similar enclosures, be filled to 60%. A sleeve through a wall is rarely between two enclosures. The calculator shows 60% for a short sleeve as a reference figure only, and the firestop listing's limit is the one it checks.

  • Do the NEC conduit fill limits apply to a sleeve?

    Often not. Chapter 9, Note 2 says Table 1 applies only to complete conduit or tubing systems, not to sections used to protect exposed wiring from physical damage. Communications, Class 2 and fire alarm cables also have their own articles, which set out when the Chapter 9 fill rules apply to them. Check the article for your cable and ask the authority having jurisdiction. The calculator's NEC figures are a reference, not a ruling.

  • How many cables fit in a sleeve?

    As many as keep the fill within your firestop listing's maximum. The calculator adds cables the size of your largest one, one at a time, and counts how many more fit before the fill passes the limit. It does the same count against the NEC reference figure.

  • Where do the cable diameters come from?

    From each cable's datasheet: its outside diameter (OD), in inches. Two cables of the same category can have different ODs, so the calculator has no built-in sizes. The example diameters are made up.

  • Does this calculator save or send what I type?

    No. The calculator runs entirely in your browser. Nothing you enter is saved or sent anywhere, and no account is needed. Copy link puts your inputs in the link itself, so only the people you send it to see them.