Ground wire size calculator

The equipment grounding conductor is sized from Table 250.122 by the rating of the breaker or fuse ahead of the circuit: a 200 A circuit needs at least 6 AWG copper. When the phase conductors were upsized, usually for voltage drop, 250.122(B) upsizes the ground wire by the same ratio of circular mils, which takes that 6 AWG to 4 AWG when 3/0 AWG phase conductors become 250 kcmil.

Enter the device rating and the ground wire's material; tick "Phase conductors were upsized" to apply 250.122(B). Based on NFPA 70, 2023 edition. It runs in your browser; nothing you type is saved or sent.

Example values, not benchmarks. Replace them with your own.

Circuit

The breaker or fuse ahead of the circuit. Any value: the next table row up is used.

Aluminum includes copper-clad aluminum.

250.122(B) upsize

The smallest size with enough ampacity, after any derating: wire ampacity calculator.

Minimum equipment grounding conductor
4 AWG copper
Table 250.122
6 AWG copper
Upsize ratio
1.4899

From the Table 250.122, 200 A row, increased by 250.122(B).

The working

table EGC          = 6 AWG copper
  Table 250.122, 200 A row (device 200 A), copper column

required phase     = 3/0 AWG copper, 167,800 cmil
installed phase    = 250 kcmil copper, 250,000 cmil
ratio              = 250,000 cmil ÷ 167,800 cmil = 1.4899
  Chapter 9 Table 8 circular mils

upsized EGC area   = 26,240 cmil × 1.4899 = 39,095 cmil
rounded up         = 4 AWG (41,740 cmil)
  250.122(B), next Table 8 size at or above that area

minimum EGC        = 4 AWG copper

How do you size an equipment grounding conductor?

Find the rating or setting of the overcurrent device ahead of the circuit in Table 250.122. Each row reads "not exceeding", so a rating between two rows takes the next one up: a 16 A device uses the 20 A row. Read the copper or the aluminum column. The equipment grounding conductor (EGC) is the wire that carries fault current back to the source so the breaker trips; it isn't required to be larger than the circuit conductors (250.122(A)).

When the phase conductors are upsized, does the ground wire go up too?

Yes. 250.122(B): when the ungrounded conductors are increased in size for any reason other than the ambient and conductor-count adjustments of 310.15(B) and (C), a wire-type EGC is increased in proportion to the increase in their circular mil area. Most lookup tables skip this step, and a long feeder upsized for voltage drop is where it bites.

ratio       = installed phase cmil ÷ required phase cmil
EGC area    = Table 250.122 EGC cmil × ratio
EGC size    = the next Chapter 9 Table 8 size at or above that area,
              no larger than the installed phase conductors (same metal),
              and never smaller than the Table 250.122 size

An example, not a recommendation: a 200 A feeder whose 3/0 AWG copper conductors are enough for the load is run in 250 kcmil for voltage drop. The ratio is 250,000 cmil ÷ 167,800 cmil = 1.4899. Table 250.122 gives 6 AWG copper (26,240 cmil), and 26,240 cmil × 1.4899 = 39,095 cmil, which rounds up to the next Table 8 size: 4 AWG copper (41,740 cmil).

Is a ground wire the same as a grounding electrode conductor?

No, and the two tables get mixed up. The grounding electrode conductor connects the service or a separately derived system to the grounding electrode (a ground rod, the building steel, a water pipe) and is sized from Table 250.66 by the largest ungrounded service-entrance or derived conductor. Bonding jumpers are sized by 250.102. This calculator sizes only the equipment grounding conductor run with a branch circuit or feeder, from Table 250.122.

Ground wire size chart (NEC Table 250.122)

Minimum size equipment grounding conductors for grounding raceway and equipment, by the rating or setting of the automatic overcurrent device ahead of the equipment, conduit, etc., not exceeding the amps shown. From NFPA 70, 2023 edition, Table 250.122. The calculator's row is highlighted.

Table 250.122 equipment grounding conductor sizes, copper and aluminum
Device rating, not exceeding Copper Aluminum or copper-clad aluminum
15 A 14 AWG 12 AWG
20 A 12 AWG 10 AWG
60 A 10 AWG 8 AWG
100 A 8 AWG 6 AWG
200 A 6 AWG 4 AWG
300 A 4 AWG 2 AWG
400 A 3 AWG 1 AWG
500 A 2 AWG 1/0 AWG
600 A 1 AWG 2/0 AWG
800 A 1/0 AWG 3/0 AWG
1,000 A 2/0 AWG 4/0 AWG
1,200 A 3/0 AWG 250 kcmil
1,600 A 4/0 AWG 350 kcmil
2,000 A 250 kcmil 400 kcmil
2,500 A 350 kcmil 600 kcmil
3,000 A 400 kcmil 600 kcmil
4,000 A 500 kcmil 750 kcmil
5,000 A 700 kcmil 1200 kcmil
6,000 A 800 kcmil 1200 kcmil

Where necessary to comply with 250.4(A)(5) or (B)(4), the equipment grounding conductor must be larger than this table gives. See 250.120 for installation restrictions. The table stops at 6,000 A.

A sizing aid, not the code. This calculator is based on NFPA 70, 2023 edition, Table 250.122, sections 250.122(A) and (B) and Chapter 9 Table 8. It is not a substitute for the code, the engineer of record or the authority having jurisdiction. Local amendments, the edition your jurisdiction has adopted and conditions the calculator doesn't model (parallel runs, motor circuits, ground-fault current path studies) can change the answer.

Related tools

  • Wire ampacity calculator: Get a conductor's allowable ampacity from NEC Table 310.16, derated for ambient and conductor count and capped at the 75 °C or 60 °C termination rating.
  • Wire size calculator: Find the smallest wire for a load from NEC Table 310.16, with the 125% continuous-load factor, 240.4(D) breaker limits and an optional voltage-drop limit.
  • Voltage drop calculator: Get a run's voltage drop in volts and percent from the NEC Chapter 9 Table 8 resistance, single- or three-phase, or the longest run that stays within a target drop.
  • Metric voltage drop calculator: Voltage drop in metres: type the cable's mV/A/m from its datasheet, the current, the length and the voltage for the drop in volts and percent, and a pass or fail against your own limit.
  • Neutral conductor size calculator: Size a feeder or service neutral from the NEC 220.61 unbalanced load, with the 70% reduction over 200 A, and the Table 250.122 or 250.102(C)(1) minimum.
  • Motor circuit calculator: wire, breaker and ground size: Size a single motor's branch circuit from NEC Article 430: full-load current, the conductor at 125%, the largest breaker or fuse, the ground wire and the overload.
  • Transformer amps calculator: Get a transformer's primary and secondary full-load amps from its kVA, phase and voltages, with a table for the standard kVA ratings.
  • Ohm's law calculator: Enter any two of voltage, current, resistance and power to get the other two, with the formula used, for DC and resistive circuits.
  • Conduit support spacing calculator: Get the NEC maximum distance between conduit supports and from a box for EMT, IMC, RMC, PVC, RTRC, ENT, FMC, LFMC and LFNC, and the minimum strap count for a run.
  • Conduit fill and size calculator: What size conduit do you need? Mix wire types and sizes, grounds included, and get the smallest conduit that fits plus the fill % in every trade size, from NEC Chapter 9.
  • Metric conduit fill calculator: Conduit fill in millimetres: type the conduit's internal diameter and each cable's overall diameter for the fill %, a pass or fail against your own limit and the largest cable that still fits.
  • Fire alarm battery calculator: Size a fire alarm panel's standby battery in amp-hours from your devices' standby and alarm currents, the NFPA 72 standby and alarm times and a safety margin.
  • Low-voltage cable footage calculator: Turn device counts into cable footage and 1,000 ft boxes: cables per device, average run and service loop per device type, plus waste, with a 295 ft check.
  • Sleeve fill calculator: How many cables fit in a sleeve through a wall: the fill % against your firestop listing's max fill, the NEC 60% nipple and Table 1 figures for reference, and how many more cables fit.
  • All free tools for electrical estimators

Questions

Frequently asked

Can't find an answer? Email contact@takeonbid.com — we read every one.

  • What size ground wire do I need for a 200 amp circuit?

    Table 250.122 gives 6 AWG copper or 4 AWG aluminum for an overcurrent device rated up to 200 A. If the phase conductors were made larger than their ampacity requires, for voltage drop for example, 250.122(B) increases the ground wire in proportion.

  • What size ground wire for a 100 amp circuit?

    8 AWG copper or 6 AWG aluminum, from the 100 A row of Table 250.122, unless the phase conductors were upsized (250.122(B)).

  • Is the equipment grounding conductor sized from the breaker or from the wire?

    From the rating or setting of the automatic overcurrent device ahead of the equipment, conduit or other raceway (250.122(A)), not from the phase conductors' ampacity. A rating between two rows uses the next row up, since each row reads 'not exceeding'.

  • When does 250.122(B) make me upsize the ground wire?

    When the ungrounded (phase) conductors are increased in size for any reason other than the ambient and conductor-count adjustments of 310.15(B) and (C), most often for voltage drop. A wire-type equipment grounding conductor is then increased in proportion to the increase in circular mil area of the ungrounded conductors. 250.122(B) also lets a qualified person size the EGC to provide an effective ground-fault current path under 250.4(A)(5) or (B)(4) instead.

  • Does the ground wire ever have to be bigger than the phase conductors?

    No. 250.122(A) says the equipment grounding conductor isn't required to be larger than the circuit conductors supplying the equipment, so when the ground wire and the phase conductors are the same metal the calculator caps an upsized EGC at the installed phase conductor size, though never below the Table 250.122 size. With copper phase conductors and an aluminum ground wire (or the reverse) their circular mil areas don't compare, so it applies no cap and gives the full proportional size, the conservative answer.

  • Is this the same as sizing a grounding electrode conductor?

    No. The grounding electrode conductor (GEC) connects the service or a separately derived system to the grounding electrode, and is sized from Table 250.66 by the largest ungrounded service-entrance or derived conductor. Bonding jumpers use 250.102. This calculator is only for the equipment grounding conductor run with a circuit.

  • Does this cover parallel runs or motor circuits?

    No. Conductors run in parallel in more than one raceway or cable follow 250.122(F), and motor circuits follow 250.122(D). Where a raceway or cable armor serves as the equipment grounding conductor (250.118), there is no wire to size.

  • Does this calculator save or send what I type?

    No. The calculator runs entirely in your browser. Nothing you enter is saved or sent anywhere, and no account is needed.