Neutral conductor size calculator

Size the neutral for the maximum unbalanced load (220.61), with the part over 200 A taken at 70%, then check it against the code minimum: Table 250.122 for a feeder (215.2(A)(2)), Table 250.102(C)(1) for a service (250.24(C)(1)). The neutral is the larger of the two.

Pick the circuit type and system, enter the unbalanced load and the minimum's input. Based on NFPA 70, 2023 edition. It runs in your browser; nothing you type is saved or sent.

Example values, not benchmarks. Replace them with your own.

Circuit

It decides the code minimum: Table 250.122 for a feeder, Table 250.102(C)(1) for a service or separately derived system (SDS) such as a transformer secondary.

2 phases + neutral of a wye (a 2-pole circuit off 208Y/120) gets no 70% reduction: 220.61(C)(1).

Neutral load

The largest load connected between the neutral and any one ungrounded conductor (220.61(A)).

Electronic ballasts, drivers, computers, VFDs. Not reduced on a 4-wire wye (220.61(C)(2)).

Neutral conductor

The lowest rating at either end; 110.14(C).

Code minimum

250.24(C)(1): Table 250.102(C)(1) sizes the neutral from it.

Neutral size
500 kcmil copper
Neutral load
340 A
Code minimum
1/0 AWG

The 220.61 load needs 500 kcmil; the code minimum is 1/0 AWG → 500 kcmil. The load governs.

CheckNeedsFrom
220.61 load 500 kcmil 380 A allowable ampacity
Code minimum 1/0 AWG Table 250.102(C)(1), copper “Over 350 through 600” row (250.24(C)(1))

220.61 sizes the neutral for the unbalanced current, which on linear loads is at most a phase's load. On a 4-wire wye with heavy nonlinear load, harmonic currents add up in the neutral and can exceed the phase current, so that neutral can need to be larger. The code minimum is never required to be larger than the largest ungrounded conductor (250.24(C)(1) for a service, 250.122(A) for a feeder), so the calculator caps it there once you enter that conductor.

The working

unbalanced load = 400 A
  220.61(A), the largest load between the neutral and any one phase
  first 200 A     200 A at 100%
  over 200 A      200 A × 0.7 = 140 A, 220.61(B)(2)
neutral load    = 200 A + 140 A = 340 A

load size       → 500 kcmil
  the smallest whose allowable ampacity is 340 A or more: 380 A
  Table 310.16 90 °C column, capped at the 75 °C column (110.14(C))
code minimum    → 1/0 AWG
  250.24(C)(1): Table 250.102(C)(1), copper “Over 350 through 600” row

neutral         = 500 kcmil copper, the larger of the two

How do you calculate the neutral load?

Start from the maximum unbalanced load: the largest load connected between the neutral and any one ungrounded conductor (220.61(A)). On a single-phase 3-wire or 3-phase 4-wire feeder or service, 220.61(B)(2) lets the part over 200 A be taken at 70%. Two cases take no reduction: the nonlinear part of the load on a 4-wire wye (220.61(C)(2)), and a circuit of 2 phases and the neutral of a 4-wire wye (220.61(C)(1)).

linear       = unbalanced − nonlinear (nonlinear: 4-wire wye only)
neutral load = nonlinear
             + the linear load up to 200 A
             + 0.7 × the linear load over 200 A

This calculator gives the 200 A at 100% to the linear load only, so no nonlinear amp is ever reduced, the conservative reading. The neutral is then the smallest conductor whose allowable ampacity (Table 310.16, capped at the termination rating by 110.14(C)) carries the neutral load.

An example, not a recommendation: a 3-phase 4-wire wye service on 600 kcmil copper phase conductors with a 400 A maximum unbalanced load, none of it nonlinear. The neutral load is 200 A + 200 A × 0.7 = 340 A, which 500 kcmil copper carries at 380 A (75 °C terminations). Without the reduction, 400 A would need 600 kcmil. The service minimum for 600 kcmil copper is 1/0 AWG (Table 250.102(C)(1), copper “Over 350 through 600” row), so the load governs and the neutral is 500 kcmil copper.

What's the smallest the neutral can be?

A feeder neutral can't be smaller than the equipment grounding conductor Table 250.122 gives for the feeder's overcurrent device (215.2(A)(2)), but it isn't required to be larger than the feeder's phase conductors (250.122(A)). That matters when the phases are smaller than the device alone implies, under the next-size-up rule (240.4(B)) or a tap rule: enter the largest phase conductor and the calculator caps the minimum there. A service neutral, or the neutral of a separately derived system such as a transformer secondary, can't be smaller than Table 250.102(C)(1) gives for the largest ungrounded conductor (250.24(C)(1), 250.30(A)(3)), because it carries the fault current back to the source. Above the table, Note 1 sets it at 12½% of the largest ungrounded conductor's area.

Which table do I use?

Which NEC table sizes the neutral, the ground wire and the grounding electrode conductor
Conductor Table Sized by
Service or SDS neutral (this page) 250.102(C)(1), minimum Largest ungrounded conductor
Feeder neutral (this page) 250.122, minimum Feeder overcurrent device
Equipment grounding conductor (ground wire calculator) 250.122 Overcurrent device ahead of the circuit
Grounding electrode conductor (not built) 250.66 Largest ungrounded service-entrance conductor

Service neutral size chart (NEC Table 250.102(C)(1))

The minimum grounded conductor, main bonding jumper, system bonding jumper and supply-side bonding jumper for AC systems, by the size of the largest ungrounded conductor (AWG / kcmil). From NFPA 70, 2023 edition, Table 250.102(C)(1). The calculator's row is highlighted for a service.

Table 250.102(C)(1) minimum grounded conductor sizes by the largest ungrounded conductor
Largest ungrounded, copper Largest ungrounded, aluminum Neutral, copper Neutral, aluminum
2 or smaller 1/0 or smaller 8 AWG 6 AWG
1 or 1/0 2/0 or 3/0 6 AWG 4 AWG
2/0 or 3/0 4/0 or 250 4 AWG 2 AWG
Over 3/0 through 350 Over 250 through 500 2 AWG 1/0 AWG
Over 350 through 600 Over 500 through 900 1/0 AWG 3/0 AWG
Over 600 through 1100 Over 900 through 1750 2/0 AWG 4/0 AWG
Over 1100 Over 1750 See Notes 1 and 2

Note 1: above 1100 kcmil copper or 1750 kcmil aluminum, the grounded conductor has an area of at least 12½% of the largest ungrounded conductor's (or the equivalent area of parallel conductors), and needn't be larger than the largest ungrounded conductor. Note 2: if the ungrounded conductors and the grounded conductor are different metals, size it as if the ungrounded conductors were the grounded conductor's metal, with equivalent ampacity. Aluminum includes copper-clad aluminum.

A sizing aid, not the code. This calculator is based on NFPA 70, 2023 edition, sections 220.61, 215.2(A)(2), 250.24(C)(1), 250.122(A), 250.30(A)(3) and 310.15(E), Tables 250.102(C)(1), 250.122 and 310.16, and Chapter 9 Table 8. It is not a substitute for the code, the engineer of record or the authority having jurisdiction. Local amendments, the edition your jurisdiction has adopted and conditions the calculator doesn't model (parallel neutrals, dwelling load calculations, harmonic loading, ambient and conductor-count derating) can change the answer.

Related tools

  • Wire ampacity calculator: Get a conductor's allowable ampacity from NEC Table 310.16, derated for ambient and conductor count and capped at the 75 °C or 60 °C termination rating.
  • Wire size calculator: Find the smallest wire for a load from NEC Table 310.16, with the 125% continuous-load factor, 240.4(D) breaker limits and an optional voltage-drop limit.
  • Voltage drop calculator: Get a run's voltage drop in volts and percent from the NEC Chapter 9 Table 8 resistance, single- or three-phase, or the longest run that stays within a target drop.
  • Metric voltage drop calculator: Voltage drop in metres: type the cable's mV/A/m from its datasheet, the current, the length and the voltage for the drop in volts and percent, and a pass or fail against your own limit.
  • Ground wire size calculator: Size the equipment grounding conductor from NEC Table 250.122, and upsize it in proportion when the phase conductors were upsized for voltage drop (250.122(B)).
  • Motor circuit calculator: wire, breaker and ground size: Size a single motor's branch circuit from NEC Article 430: full-load current, the conductor at 125%, the largest breaker or fuse, the ground wire and the overload.
  • Transformer amps calculator: Get a transformer's primary and secondary full-load amps from its kVA, phase and voltages, with a table for the standard kVA ratings.
  • Ohm's law calculator: Enter any two of voltage, current, resistance and power to get the other two, with the formula used, for DC and resistive circuits.
  • Conduit support spacing calculator: Get the NEC maximum distance between conduit supports and from a box for EMT, IMC, RMC, PVC, RTRC, ENT, FMC, LFMC and LFNC, and the minimum strap count for a run.
  • Conduit fill and size calculator: What size conduit do you need? Mix wire types and sizes, grounds included, and get the smallest conduit that fits plus the fill % in every trade size, from NEC Chapter 9.
  • Metric conduit fill calculator: Conduit fill in millimetres: type the conduit's internal diameter and each cable's overall diameter for the fill %, a pass or fail against your own limit and the largest cable that still fits.
  • Fire alarm battery calculator: Size a fire alarm panel's standby battery in amp-hours from your devices' standby and alarm currents, the NFPA 72 standby and alarm times and a safety margin.
  • Low-voltage cable footage calculator: Turn device counts into cable footage and 1,000 ft boxes: cables per device, average run and service loop per device type, plus waste, with a 295 ft check.
  • Sleeve fill calculator: How many cables fit in a sleeve through a wall: the fill % against your firestop listing's max fill, the NEC 60% nipple and Table 1 figures for reference, and how many more cables fit.
  • All free tools for electrical estimators

Questions

Frequently asked

Can't find an answer? Email contact@takeonbid.com — we read every one.

  • How do you size a neutral conductor?

    Two checks, and the neutral is the larger. First the load: 220.61 sizes the neutral for the maximum unbalanced load, the largest load between the neutral and any one ungrounded conductor, with the part over 200 A permitted at 70% (220.61(B)(2)). Pick the smallest conductor whose allowable ampacity carries that. Then the code minimum: a feeder neutral can't be smaller than the Table 250.122 equipment grounding conductor for its overcurrent device (215.2(A)(2)), though like that conductor it isn't required to be larger than the feeder's phase conductors (250.122(A)), and a service or separately derived system neutral can't be smaller than Table 250.102(C)(1) gives for the largest ungrounded conductor (250.24(C)(1), 250.30(A)(3)).

  • Can the neutral be smaller than the hot conductors?

    Yes, when the unbalanced load is smaller than the phase load or the 70% reduction applies, as long as it meets the code minimum. In the example on this page a 400 A unbalanced load counts as 340 A, so the neutral is 500 kcmil on 600 kcmil phase conductors. It can't be reduced for the nonlinear part of the load on a 3-phase 4-wire wye (220.61(C)(2)), or on a circuit of 2 phases and the neutral of a 4-wire wye (220.61(C)(1)).

  • What is the 70% neutral reduction?

    220.61(B)(2) lets the part of the unbalanced load over 200 A be taken at 70% on a single-phase 3-wire or 3-phase 4-wire feeder or service: the first 200 A at 100%, the rest at 70%. 400 A becomes 200 A + 200 A × 0.7 = 340 A. 220.61(B)(1) has a separate 70% for household ranges and dryers in a dwelling calculation, which this calculator doesn't apply.

  • Does the neutral count as a current-carrying conductor?

    Usually not. A neutral that carries only the unbalanced current of the other conductors isn't counted (310.15(E)(1)). It is counted on a circuit of 2 phases and the neutral of a 4-wire wye, where it carries about the same current as the phases (310.15(E)(2)), and on a 4-wire 3-phase wye where the major portion of the load is nonlinear (310.15(E)(3)). Then use it in the conductor count for the adjustment factors.

  • Is the neutral the same size as the ground wire?

    Not necessarily. The equipment grounding conductor is sized from Table 250.122 by the overcurrent device (a 200 A feeder needs at least 6 AWG copper). The neutral carries load, so it is sized for the 220.61 load, and Table 250.122 is only its floor on a feeder. On a service the floor is Table 250.102(C)(1) instead, and the grounding electrode conductor is a third table, 250.66.

  • What if the service conductors are larger than 1100 kcmil?

    Above the table (over 1100 kcmil copper or 1750 kcmil aluminum), Note 1 to Table 250.102(C)(1) sets the grounded conductor at no less than 12½% of the area of the largest ungrounded conductor. If the neutral and the phase conductors are different metals, Note 2 sizes it from a phase conductor of the neutral's metal with equivalent ampacity.

  • Does this cover parallel neutrals or dwelling services?

    No. Parallel conductor sets (310.10(G)), the 2-phase systems, the dwelling-unit load calculations of Article 220 Parts III and IV, and harmonic oversizing beyond the 220.61(C) and 310.15(E) rules aren't modelled. It sizes one neutral conductor from the load you enter.

  • Does this calculator save or send what I type?

    No. The calculator runs entirely in your browser. Nothing you enter is saved or sent anywhere, and no account is needed.